[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-110-1-water-chemical-034":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-110-1-水與化學系統消防安全設備概要-034","fire-110-1-water-chemical-034",110,1,34,"依消防安全設備及必要檢修項目檢修基準，乾粉加壓式滅火器性能檢查之檢查抽樣頻率，應幾年實施一次性能檢查？",{"A":16,"B":17,"C":18,"D":19},"1","2","3","4","C",null,[],false,"本題考點：《檢修基準》滅火器性能檢查的檢查頻率，依滅火器種類二分為每年一次與每三年一次。\n【正解理由】依《消防安全設備及必要檢修項目檢修基準》第一章滅火器性能檢查之檢查抽樣、檢查頻率，「依滅火器種類，化學泡沫滅火器應每年實施一次性能檢查，其餘類型滅火器應每三年實施一次性能檢查，並依表 1-2 之規定進行」。乾粉加壓式滅火器不屬化學泡沫，落在「其餘類型滅火器」，故選 C。\n【逐項排除】\n(A) 1：一年一次是原文專就化學泡沫滅火器所定的頻率，本題問的是乾粉加壓式，不適用該款。\n(B) 2：檢查頻率原文只列「每年」與「每三年」兩種週期，並無兩年一次之規定。\n(C) 3：乾粉加壓式屬「其餘類型滅火器」，適用每三年實施一次性能檢查，為本題應選者。\n(D) 4：原文未定四年之週期；表 1-2 中與乾粉相關的數字是抽樣對象條件「自製造年份起超過三年以上者」，其檢查試樣個數為全數，仍指向三。\n【記憶點】性能檢查頻率二分法：化學泡沫每年一次，其餘（水、強化液、機械泡、鹵化物、二氧化碳、乾粉）每三年一次。","檢查頻率只是入口，真正決定「哪幾支要拆」的是表 1-2 檢查試樣個數表。該表以種類與加壓方式交叉列出對象與試樣數：水滅火器（加壓式、蓄壓式）與強化液滅火器（加壓式、蓄壓式）為自製造年份起超過三年以上者、全數；化學泡加壓式為設置達一年以上者、全數；機械泡（加壓式、蓄壓式）為自製造年份起超過三年以上者、全數；鹵化物與二氧化碳為自製造年份起超過三年以上者，如重量及指示壓力值無異常時，其它項目可予省略；乾粉（加壓式、蓄壓式）為自製造年份起超過三年以上者、全數；全部之滅火器如經外觀檢查有缺點者，須進行性能檢查、全數。表下備註另定製造日期超過十年或無法辨識製造日期之水滅火器、機械泡沫滅火器或乾粉滅火器，非經水壓測試合格，不得再行更換及充填藥劑，應予報廢。\n加壓式滅火器的性能檢查順序也有固定體例：藥劑量以重量表示者以磅秤確認總重量，有排氣閥者先打開使容器內壓完全排出，卸下護蓋取出加壓用氣體容器之支撐裝置及加壓用氣體容器，藥劑量以容量表示者確認是否達液面標示之定量位置，取出藥劑移置另一容器，再行清理與確認各構件；其中水系滅火器以清水洗滌，鹵化物滅火器或乾粉滅火器屬嚴禁水分之物質，應以乾燥之壓縮空氣清理本體容器內外、護蓋、噴射皮管、噴嘴及虹吸管。\n檢查結果的判定分兩路：未發現缺點者視為良好；發現缺點者應即進行檢修或更新，泡沫滅火藥劑因經較長時間會產生變化，依銘板標示時間或製造商使用規範定期更換，其餘類型滅火藥劑若無固化結塊、異物、沉澱物、變色、污濁或異臭，可繼續使用。完成性能檢查後應依表 1-1 格式張貼標示，並於瓶頸加裝檢修環，顏色以紅、橙、黃、綠、藍交替，自一百一十年度起使用紅色，一百一十一年度橙色、一百一十二年度黃色、一百一十三年度綠色、一百一十四年度藍色，依此類推。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-110-1-water-chemical-033","依消防安全設備及必要檢修項目檢修基準，滅火器設置間距規定，下列何者錯誤？",33,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-110-1-water-chemical-035","依消防安全設備及必要檢修項目檢修基準，製造日期超過 10 年或無法辨識製造日期之何種滅火器，非經水壓測試合格，不得再行更換及充填藥劑，應予報廢？",35,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-110-1-water-chemical-032","公共危險物品等場所消防設計及消防安全設備，有關設置冷卻撒水設備規定，下列何者正確？",32,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-110-1-water-chemical-036","依消防安全設備及必要檢修項目檢修基準，自動撒水設備之加壓送水裝置，在減壓措施方面，補助撒水栓放水壓力應在 X kgf\u002Fcm2 以上 Y kgf\u002Fcm2 以下。X、Y 分別為何？",36,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-110-1-water-chemical-031","公共危險物品等場所消防設計及消防安全設備，室外消防栓設備採用鑄鐵管配管時，使用符合 CNS 832 規定之壓力管路鑄鐵管或具同等以上強度者，其標稱壓力在每平方公分多少公斤以上？",31,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-110-1-water-chemical-037","依消防安全設備及必要檢修項目檢修基準，水道連結型自動撒水設備之末端查驗閥或連結之水龍頭等日常生活用水設施配置的壓力表，其放水壓力應在 X kgf\u002Fcm2 以上 Y kgf\u002Fcm2 以下。X、Y 分別為何？",37,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-034",111,"第五種滅火設備除滅火器外之其他設備，有關滅火效能值核算之規定，下列何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-water-chemical-034",109,"乾粉滅火設備使用加壓或蓄壓用氣體容器，其所使用之氣體為下列何者？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-water-chemical-034",108,"依各類場所消防安全設備設置標準之規定，水霧滅火設備之加壓送水裝置使用消防幫浦時，用於防護電氣設備者，每一個水霧噴頭壓力依規定均應達到多少以上？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-water-chemical-034",107,"依 NFPA 2001 之規定，潔淨式氣體滅火系統於一般場所之藥劑放射時間（達設計濃度 95%之時間），下列敘述何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-water-chemical-034",106,"第一種乾粉滅火藥劑，全區放射方式所需滅火藥劑量為多少 kg\u002Fm ？",1785123166848]