[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-110-1-water-chemical-037":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-110-1-水與化學系統消防安全設備概要-037","fire-110-1-water-chemical-037",110,1,37,"依消防安全設備及必要檢修項目檢修基準，水道連結型自動撒水設備之末端查驗閥或連結之水龍頭等日常生活用水設施配置的壓力表，其放水壓力應在 X kgf\u002Fcm2 以上 Y kgf\u002Fcm2 以下。X、Y 分別為何？",{"A":16,"B":17,"C":18,"D":19},"X=1；Y=6","X=1；Y=10","X=0.5；Y=6","X=0.5；Y=10","D",null,[],false,"本題考點：《檢修基準》水道連結型自動撒水設備綜合檢查，末端查驗閥或日常生活用水設施處壓力表的放水壓力判定範圍。\n【正解理由】依《消防安全設備及必要檢修項目檢修基準》第五章水道連結型自動撒水設備綜合檢查之判定方法，「末端查驗閥或連結之水龍頭等日常生活用水設施配置的壓力表，其放水壓力應在 0.5kgf\u002Fcm² 以上 10kgf\u002Fcm² 以下」，故選 D。\n【逐項排除】\n(A) X=1；Y=6：1 kgf\u002Fcm² 是第四章自動撒水設備綜合檢查中，密閉式撒水設備末端查驗管放水壓力的下限；6 kgf\u002Fcm² 亦非第五章所定之上限，兩個數字都不屬本章。\n(B) X=1；Y=10：1 以上 10 以下是第四章密閉式撒水設備末端查驗管的放水壓力範圍，水道連結型自動撒水設備另立專章，下限並非 1。\n(C) X=0.5；Y=6：下限 0.5 與第五章判定方法相符，但該章所定上限為 10kgf\u002Fcm²，不是 6。\n(D) X=0.5；Y=10：與第五章判定方法逐字相符，為本題應選者。\n【記憶點】末端放水壓力依章分記：第四章一般密閉式撒水 1～10，第五章水道連結型 0.5～10，單位皆為 kgf\u002Fcm²。","水道連結型自動撒水設備的法源起點在《設置標準》第 17 條第三項：第一項第九款所定榮譽國民之家、長期照顧服務機構、老人福利機構、護理機構、身心障礙福利機構等場所，其樓地板面積合計未達一千平方公尺者，得設置水道連結型自動撒水設備或與現行法令同等以上效能之滅火設備，或採用中央主管機關公告之措施；其設置基準由中央消防機關定之。這類設備直接連接日常生活用水管路，設計壓力與一般自動撒水設備不同，檢修判定值也因此另立一章。\n第五章綜合檢查的檢查方法規定，於建築物各層放水壓力最低之最遠支管末端，打開末端查驗閥或連結之水龍頭等日常生活用水設施，確認系統性能是否正常及壓力表之指示值；設置末端查驗閥者，應設有與撒水頭同等放水性能之限流孔；設有增壓供水裝置者，於打開末端查驗閥或水龍頭等日常生活用水設施降低配管內壓力後，該增壓供水裝置應開始動作。判定方法分兩項：放水壓力應在 0.5kgf\u002Fcm² 以上 10kgf\u002Fcm² 以下；增壓供水裝置（限有裝設者）應能確實啟動，且運轉中應無不規則、不連續之雜音或異常之振動、發熱等。\n末端查驗閥本身的構造規定在《設置標準》第 56 條：使用密閉式撒水頭之自動撒水設備末端之查驗閥，管徑在二十五毫米以上；依各流水檢知裝置配管系統配置，並接裝在建築物各層放水壓力最低之最遠支管末端；一次側設壓力表，二次側設有與撒水頭同等放水性能之限流孔；距離地板面之高度在二點一公尺以下，並附有排水管裝置，並標明末端查驗閥字樣。檢修時之所以要選「最遠支管末端」，正是因為該處放水壓力最低，能反映系統最不利點是否仍達判定下限。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-110-1-water-chemical-036","依消防安全設備及必要檢修項目檢修基準，自動撒水設備之加壓送水裝置，在減壓措施方面，補助撒水栓放水壓力應在 X kgf\u002Fcm2 以上 Y kgf\u002Fcm2 以下。X、Y 分別為何？",36,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-110-1-water-chemical-038","依消防安全設備及必要檢修項目檢修基準，海龍滅火設備全區放射方式檢查方法，若以空氣或氮氣進行放射試驗，所需空氣量或氮氣量，應就放射區域應設滅火藥劑量之多少%核算？",38,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-110-1-water-chemical-035","依消防安全設備及必要檢修項目檢修基準，製造日期超過 10 年或無法辨識製造日期之何種滅火器，非經水壓測試合格，不得再行更換及充填藥劑，應予報廢？",35,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-110-1-water-chemical-039","依消防安全設備及必要檢修項目檢修基準，冷卻撒水設備之遠隔啟動裝置，限用於儲存閃火點多少℃以下公共危險物品之室外儲槽？",39,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-110-1-water-chemical-034","依消防安全設備及必要檢修項目檢修基準，乾粉加壓式滅火器性能檢查之檢查抽樣頻率，應幾年實施一次性能檢查？",34,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-110-1-water-chemical-040","依消防安全設備及必要檢修項目檢修基準，冷卻撒水設備之供第四類公共危險物品之顯著滅火困難場所之加壓送水裝置，啟動後 X 分鐘內應能有效撒水，且加壓送水裝置距撒水區域在 Y 公尺以下，但設有保壓措施者不在此限。X、Y 分別為何？",40,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-111-1-water-chemical-037",111,"依規定 112 年度滅火器檢查合格時，應採用那種顏色檢修環？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-water-chemical-037",109,"連結送水管之配管設置規定，應能承受送水設計壓力 1.5 倍以上之水壓，且能持續多少時間才合格？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-water-chemical-037",108,"進行滅火器之檢查時，有關一般注意事項，下列何者錯誤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-water-chemical-037",107,"有關撒水頭設置之敘述，下列何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-water-chemical-037",106,"消防幫浦之全閉揚程應為性能曲線上全揚程之百分之多少以下，方符合檢修基準要求？",1785123166879]