[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-110-1-water-chemical-039":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-110-1-水與化學系統消防安全設備概要-039","fire-110-1-water-chemical-039",110,1,39,"依消防安全設備及必要檢修項目檢修基準，冷卻撒水設備之遠隔啟動裝置，限用於儲存閃火點多少℃以下公共危險物品之室外儲槽？",{"A":16,"B":17,"C":18,"D":19},"40","50","70","100","C",null,[],false,"本題考點：《消防安全設備及必要檢修項目檢修基準》冷卻撒水設備章，遠隔啟動裝置所限定之公共危險物品閃火點門檻。\n【正解理由】依《消防安全設備及必要檢修項目檢修基準》第二十五章冷卻撒水設備，其外觀檢查與性能檢查之啟動裝置項下，均就遠隔啟動裝置逐字括註「限用於儲存閃火點 70℃以下公共危險物品之室外儲槽」，門檻即攝氏七十度，故選 C。\n【逐項排除】\n(A) 40℃：候選原文之攝氏四十度見於《各類場所消防安全設備設置標準》第 215 條，係室外儲槽增設泡沫射水槍滅火設備之適用門檻，與遠隔啟動裝置無涉。\n(B) 50℃：檢修基準冷卻撒水設備章與設置標準第 216 條均無此數值，屬憑印象作答之干擾項。\n(C) 70℃：與檢修基準之括註相符，並與第 216 條所定冷卻撒水設備適用於「閃火點在攝氏七十度以下之第四類公共危險物品」之範圍一致。\n(D) 100℃：候選原文之攝氏一百度見於第 194 條、第 195 條，係高閃火點物品操作溫度之判定用語，與本設備之啟動裝置無關。\n【記憶點】冷卻撒水設備看七十度，遠隔啟動裝置的括註就寫在檢修基準啟動裝置那一項。","《設置標準》第 216 條是冷卻撒水設備的母條文：以室內、室外儲槽儲存閃火點在攝氏七十度以下之第四類公共危險物品之顯著滅火困難場所，除設置固定式泡沫滅火設備外，並應設冷卻撒水設備。同條並定撒水噴孔孔徑在四毫米以上、撒水管設於槽壁頂部（儲槽設有風樑或補強環等阻礙水路徑者於其下方增設）、撒水量按槽壁總防護面積每平方公尺每分鐘二公升以上計算、水源容量在最大一座儲槽連續放水四小時之水量以上、選擇閥或開關閥設於防液堤外且操作位置距地面零點八公尺以上一點五公尺以下。啟動裝置分兩層：手動啟動裝置之操作部設於加壓送水裝置設置之場所；遠隔啟動裝置則由開啟選擇閥使啟動用水壓開關裝置或流水檢知裝置連動啟動，或設於監控室等平常有人駐守處所直接啟動，並附「送水區域距加壓送水裝置在三百公尺以內者，得免設遠隔啟動裝置」之但書。檢修基準第二十五章之綜合檢查則以放射量Ｑ＝Ｋ√Ｐ核算，並列三個判定值：公共危險物品室外儲槽場所實測放射量除以所防護儲槽側壁面積應在 2 l\u002Fmin·m² 以上；可燃性高壓氣體場所、加氣站、天然氣儲槽及可燃性高壓氣體儲槽場所除以防護面積應在 5 l\u002Fmin·m² 以上；其中以厚度 25mm 以上岩棉等隔熱材被覆、外側再以 0.35mm 以上鋅鐵板被覆者為 2.5 l\u002Fmin·m² 以上。三個值分屬不同場所與被覆條件，命題常拆開單問。顯著滅火困難場所之認定另見第 194 條，室外儲槽場所以儲槽儲存液體表面積、儲槽高度等要件判斷。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-110-1-water-chemical-038","依消防安全設備及必要檢修項目檢修基準，海龍滅火設備全區放射方式檢查方法，若以空氣或氮氣進行放射試驗，所需空氣量或氮氣量，應就放射區域應設滅火藥劑量之多少%核算？",38,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-110-1-water-chemical-040","依消防安全設備及必要檢修項目檢修基準，冷卻撒水設備之供第四類公共危險物品之顯著滅火困難場所之加壓送水裝置，啟動後 X 分鐘內應能有效撒水，且加壓送水裝置距撒水區域在 Y 公尺以下，但設有保壓措施者不在此限。X、Y 分別為何？",40,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-110-1-water-chemical-037","依消防安全設備及必要檢修項目檢修基準，水道連結型自動撒水設備之末端查驗閥或連結之水龍頭等日常生活用水設施配置的壓力表，其放水壓力應在 X kgf\u002Fcm2 以上 Y kgf\u002Fcm2 以下。X、Y 分別為何？",37,{"webId":41,"stem":42,"number":12,"year":43,"session":12},"fire-111-1-water-chemical-001","依各類場所消防安全設備設置標準規定，下列何種場所不需設置室外消防栓設備？",111,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-110-1-water-chemical-036","依消防安全設備及必要檢修項目檢修基準，自動撒水設備之加壓送水裝置，在減壓措施方面，補助撒水栓放水壓力應在 X kgf\u002Fcm2 以上 Y kgf\u002Fcm2 以下。X、Y 分別為何？",36,{"webId":49,"stem":50,"number":51,"year":43,"session":12},"fire-111-1-water-chemical-002","有關室外消防栓與室內消防栓之瞄子放水壓力之敘述，下列何者正確？",2,[53,56,60,64,68],{"webId":54,"year":43,"stem":55,"number":13},"fire-111-1-water-chemical-039","可燃性高壓氣體儲存場所任一點至滅火器之步行距離在 X 公尺以下，並不得妨礙出入作業；每具滅火器對普通火災具有 Y 個以上之滅火效能值，請問前述 X、Y 為何？",{"webId":57,"year":58,"stem":59,"number":13},"fire-109-1-water-chemical-039",109,"公共危險品等場所中，所設置之室外消防栓設備，其緊急電源之供電容量應供其有效動作多久以上？",{"webId":61,"year":62,"stem":63,"number":13},"fire-108-1-water-chemical-039",108,"依各類場所消防安全設備設置標準之規定，公共危險物品室外儲槽場所之冷卻撒水設備如以幫浦方式進行加壓時，實際測得之放射量除以該冷卻撒水噴頭（噴孔）所防護儲槽側壁面積應在多少以上？",{"webId":65,"year":66,"stem":67,"number":13},"fire-107-1-water-chemical-039",107,"為執行檢修申報，針對水霧滅火系統綜合檢查，對於判定方法之敘述，下列何者正確？",{"webId":69,"year":70,"stem":71,"number":13},"fire-106-1-water-chemical-039",106,"泡沫滅火設備使用低發泡水成膜泡沫液，其泡沫 25%還原時間應在多少分鐘以上？",1785123166900]