[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-111-1-alarm-evacuation-012":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":25,"sameNumber":50,"hasEssay":68},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":24,"freq":12,"indexable":23},"fire-111-1-警報與避難系統消防安全設備概要-012","fire-111-1-alarm-evacuation-012",111,1,12,"某餐廳廚房之瓦斯爐具使用天然氣作為燃料時，依法設有瓦斯漏氣火警自動警報設備，其瓦斯漏氣檢知器應設於距瓦斯爐具水平距離 X 公尺以內，且於該水平距離內之天花板無淨高 Y 公分以上之樑或類似構造體區隔之吸氣口 Z 公尺範圍內，試問Ｘ、Ｙ、Z 分別為何？",{"A":16,"B":17,"C":18,"D":19},"X=4、Y=40、Z=1","X=8、Y=60、Z=1.5","X=4、Y=60、Z=1","X=8、Y=40、Z=1.2","B",null,[],false,"",[26,31,35,39,43,47],{"webId":27,"stem":28,"number":29,"year":30,"session":12},"fire-106-1-alarm-evacuation-008","天花板設排氣口或回風口時，偵煙式探測器應裝置於排氣口或回風口周圍多少距離範圍內？",8,106,{"webId":32,"stem":33,"number":34,"year":30,"session":12},"fire-106-1-alarm-evacuation-010","緩降機設置周圍為避免有操作障礙，因此限制必要操作面積為 M 平方公尺以上（不含避難器具所占面積），但邊長應為 N 公分以上。下列何者正確？",10,{"webId":36,"stem":37,"number":38,"year":30,"session":12},"fire-106-1-alarm-evacuation-007","如設置救助袋做為避難器具，下列敘述何者錯誤？",7,{"webId":40,"stem":41,"number":42,"year":30,"session":12},"fire-106-1-alarm-evacuation-011","Ｐ型受信總機採用數個分區共用一公用線方式配線時，該公用線供應之分區數，不得超過 X 個。受信總機之探測器回路電阻，應在 Y 以下。下列何者正確？",11,{"webId":44,"stem":45,"number":46,"year":30,"session":12},"fire-106-1-alarm-evacuation-006","樓梯、斜坡通道、昇降機之昇降路及管道間等場所，其頂層相差在二層以下、水平距離多少範圍內，視為一火警分區？",6,{"webId":48,"stem":49,"number":13,"year":30,"session":12},"fire-106-1-alarm-evacuation-012","依據緊急照明燈認可基準進行充電試驗時，蓄電池電壓降達額定電壓多少以內時，需能自動充電？",[51,55,59,63,67],{"webId":52,"year":53,"stem":54,"number":13},"fire-110-1-alarm-evacuation-012",110,"建築物某一樓層（A 區）通往直通樓梯（B 區）的出口標示燈（L）附有誘導音裝置，並設置有停止專用偵煙式探測器（D）及具有緊急廣播設備連動停止性能，在其性能試驗之連動停止試驗中，下列何者應判定不合格？",{"webId":56,"year":57,"stem":58,"number":13},"fire-109-1-alarm-evacuation-012",109,"有關緊急電源插座之設置規定，下列敘述何者正確？",{"webId":60,"year":61,"stem":62,"number":13},"fire-108-1-alarm-evacuation-012",108,"有關依各類場所消防安全設備設置標準規定設置之耐燃保護、耐熱保護措施，室內消防栓、室外消防栓、自動撒水、水霧、泡沫、乾粉、二氧化碳滅火設備、連結送水管設備等之配管，於實施施工、加壓試驗及配合建築物樓地板、樑、柱、牆施工須預埋消防管線時，消防專技人員何人應一併拍照建檔存證以供消防機關查核，消防機關並得視需要隨時派員前往查驗？",{"webId":64,"year":65,"stem":66,"number":13},"fire-107-1-alarm-evacuation-012",107,"有關光電式分離型探測器光軸，下列設置規定何者正確？",{"webId":48,"year":30,"stem":49,"number":13},true,1785123170342]