[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-111-1-alarm-evacuation-033":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":25,"sameNumber":50,"hasEssay":68},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":24,"freq":12,"indexable":23},"fire-111-1-警報與避難系統消防安全設備概要-033","fire-111-1-alarm-evacuation-033",111,1,33,"依消防安全設備測試報告書測試方法及判定要領，有關瓦斯漏氣火警自動警報設備檢知器之動作試驗，以加瓦斯試驗器將試驗瓦斯加進檢知器，測定至瓦斯漏氣表示為止之時間，下列何者正確？",{"A":16,"B":17,"C":18,"D":19},"依檢知器動作標示燈確認檢知器之瓦斯漏氣動作者，從動作確認燈亮燈至瓦斯漏氣燈亮燈之時間，應在 60 秒以內（有使用中繼器）","依檢知區域警報裝置之動作，確認檢知器之瓦斯漏氣動作者，從檢知區域警報裝置之動作至瓦斯漏氣燈亮燈之時間，應在 65 秒以內（無使用中繼器）","依中繼器之確認燈之動作，確認檢知器之瓦斯漏氣動作者，從中繼器之動作確認燈亮燈至瓦斯漏氣燈亮燈之時間，應在 85 秒以內（有使用中繼器）","無法由檢知器動作標示燈或檢知區域警報裝置或中繼器之動作確認燈測定者，至瓦斯漏氣表示之時間，應在 80 秒以內（無使用中繼器）","D",null,[],false,"",[26,31,35,39,43,47],{"webId":27,"stem":28,"number":29,"year":30,"session":12},"fire-106-1-alarm-evacuation-029","瓦斯濃度達到警報濃度值後，其濃度仍繼續存在，即發出警報，但瓦斯洩漏濃度越高，則警報延遲動作時間越短，此種檢知瓦斯之警報發出方式稱作何種型式？",29,106,{"webId":32,"stem":33,"number":34,"year":30,"session":12},"fire-106-1-alarm-evacuation-031","在某飯店檢查瓦斯漏氣火警自動警報設備，進行檢知器之性能檢查時，發現同一個檢知回路上裝設有 18 個瓦斯漏氣檢知器，至少應選取多少個進行試驗？",31,{"webId":36,"stem":37,"number":38,"year":30,"session":12},"fire-106-1-alarm-evacuation-028","大型建築物警報設備使用許多中繼器來連結探測器與受信總機，但下列何者不是警報設備中繼器主要功能？",28,{"webId":40,"stem":41,"number":42,"year":30,"session":12},"fire-106-1-alarm-evacuation-032","針對瓦斯漏氣火警自動警報設備進行性能檢查，使用噪音計進行瓦斯漏氣檢知區域警報裝置之音量檢測時，距離警報裝置 1 公尺處，其音壓量應在多少分貝以上方為合格？",32,{"webId":44,"stem":45,"number":46,"year":30,"session":12},"fire-106-1-alarm-evacuation-027","避難方向指示燈設於樓梯或坡道者，在樓梯級面或坡道表面之照度，應在多少勒克司（lx）以上？",27,{"webId":48,"stem":49,"number":13,"year":30,"session":12},"fire-106-1-alarm-evacuation-033","針對某百貨公司美食街進行檢修，下列何項試驗必須使用加瓦斯試驗器，使兩個回路之任一檢知器（各回路一個）同時動作，以確認其性能是否異常？",[51,55,59,63,67],{"webId":52,"year":53,"stem":54,"number":13},"fire-110-1-alarm-evacuation-033",110,"緩降機在進行綜合檢查之下降試驗時，以測量下降距離及下降時間計算出下降速度，平均下降速度何者正確？",{"webId":56,"year":57,"stem":58,"number":13},"fire-109-1-alarm-evacuation-033",109,"有關緊急電源插座外觀檢查之判定方法，下列何者與各類場所消防安全設備檢修及申報作業基準之規定不同？",{"webId":60,"year":61,"stem":62,"number":13},"fire-108-1-alarm-evacuation-033",108,"有關 B 級出口標示燈（顯示避難方向符號者）及 B 級避難方向指示燈有效範圍的規定，下列何者正確？",{"webId":64,"year":65,"stem":66,"number":13},"fire-107-1-alarm-evacuation-033",107,"依各類場所消防安全設備檢修及申報作業基準規定，檢查檢知器時，使用「加瓦斯試驗器」進行加瓦斯測試，對空氣之比重未滿一者應使用何種物質？",{"webId":48,"year":30,"stem":49,"number":13},true,1785123170545]