[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-fire-law-012":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-消防法規概要-012","fire-111-1-fire-law-012",111,1,12,"消防幫浦加壓送水裝置中，有關呼水裝置規定之敘述，下列何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"呼水裝置須具備減水警報裝置","呼水槽底與呼水管逆止閥中心線間距離在 1 公尺以下時，呼水管管徑須為 40A 以上","呼水槽水位降至其容量三分之一前，應能發出警報音響至平時有人駐在處","呼水裝置應有 100 公升以上之有效儲存量","C",null,[],false,"本題考點：《消防幫浦加壓送水裝置等及配管摩擦損失計算基準》就呼水裝置所定之機件、有效儲存量、配管管徑與減水警報之動作水位。\n【正解理由】該基準呼水裝置一節明定，減水警報之發訊裝置應採用浮筒開關或電極方式，當呼水槽水位降至其容量二分之一前，應能發出警報音響至平時有人駐在處；《消防安全設備及必要檢修項目檢修基準》第二章室內消防栓設備、第四章自動撒水設備之性能檢查，其呼水裝置判定方法亦一致載明水量減少到一半時應發出警報。C 寫成三分之一，動作水位與規定不符，為敘述錯誤者，故選 C。\n【逐項排除】\n(A) 呼水裝置須具備呼水槽、溢水用排水管、補給水管、呼水管、減水警報裝置及自動給水裝置，減水警報裝置為法定機件之一，敘述正確。\n(B) 呼水管管徑標準為 25A，但呼水槽底與呼水管逆止閥中心線間距離在 1 公尺以下時，須為 40A 以上，敘述正確。\n(C) 減水警報應於水位降至容量二分之一前發出，而非三分之一，敘述錯誤，為本題應選者。\n(D) 呼水裝置應有 100 公升以上之有效儲存量，敘述正確。\n【記憶點】呼水槽記「一百公升、二分之一報警、貼近逆止閥就放大到 40A」。","呼水裝置的存在理由，是水源水位低於幫浦位置時，幫浦與吸水配管內若失水便會空轉而無法起水，因此需常時充水於幫浦及配管。《設置標準》第 37 條把加壓送水裝置分為重力水箱、壓力水箱與消防幫浦三者擇一設置，只有消防幫浦這一種在水源低於幫浦時才需要呼水裝置與底閥，重力水箱靠必要落差、壓力水箱靠水箱內空氣占容積三分之一以上之壓力，體例本就不同。管徑之所以在呼水槽底與呼水管逆止閥中心線間距離一公尺以下時要由 25A 放大為 40A，是因為落差小則補水的驅動水頭小，需以較大管徑降低摩擦損失，才能確保逆止閥前端持續維持滿水。減水警報訂在容量二分之一，則是刻意留一半水量作為緩衝，讓警報發到平時有人駐在處後仍有處理時間，這也是判定基準把動作點寫成「降至其容量二分之一前」而非「水用完前」的原因。檢修面的延伸考點在《消防安全設備及必要檢修項目檢修基準》各設備章的性能檢查：閥類以手實地操作確認開、關動作是否容易進行；自動給水裝置打開排水閥確認能否自動給水；減水警報裝置關閉補給水閥再打開排水閥，確認水量減少到一半時是否發出警報；底閥則拉上吸水管或檢查用鍊條確認有無異物附著或阻塞，並打開幫浦本體上呼水漏斗之制水閥，確認能否連續溢水、關閉呼水管制水閥後其逆止效果是否正常。此外《防火牆及防火水幕設置基準》第 11 點明定，防火水幕設備之緊急電源、消防幫浦加壓送水裝置及配管摩擦損失等，本基準未規定者準用「緊急電源容量計算基準」及「消防幫浦加壓送水裝置等及配管摩擦損失計算基準」，可見呼水裝置規格會被其他基準反覆援用。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-fire-law-011","有關二氧化碳滅火設備使用之各種標示規格，下列敘述何者錯誤？",11,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-fire-law-013","某建築物設置收納金屬製避難梯為避難器具，其升降口之施工方法何者錯誤？",13,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-fire-law-010","依各類場所消防安全設備檢修期限及申報備查期限，下列敘述何者錯誤？",10,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-fire-law-014","下列那一場所不是應設置無線電通信輔助設備之場所？",14,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-fire-law-009","有關室內儲槽場所幫浦設備之設置規定，下列敘述何者錯誤？",9,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-fire-law-015","某一百貨商場為地上八層、地下三層，總樓地板面積 3 千平方公尺。其火警自動警報設備之鳴動方式何者錯誤？",15,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-fire-law-012",110,"依公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法之規定，有關公共危險物品及其製造、儲存場所之規定，下列敘述何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-fire-law-012",109,"依公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法，有關於供作六類物品製造場所或一般處理場所使用之建築物，一部分供作室內儲存場所儲存六類物品之數量在管制量 20 倍以下者，其牆壁、樑、柱、地板及上層之地板應為防火構造，且應具有多少小時以上防火時效？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-fire-law-012",108,"依據各類場所消防安全設備設置標準規定，設於儲槽之固定式泡沫滅火設備，下列何者係指供固定頂儲槽槽底注入泡沫法之放出口？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-fire-law-012",107,"依建築技術規則建築設計施工編之規定，經中央主管建築機關認定符合耐燃二級之材料，屬於下列何種建築材料？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-fire-law-012",106,"依據公共危險物品及可燃性高壓氣體設置標準暨安全管理辦法規定，下列何種公共危險物品，不得儲放室外儲存場所？",1785123157374]