[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-fire-law-016":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-消防法規概要-016","fire-111-1-fire-law-016",111,1,16,"防災監控系統綜合操作裝置之緊急電源供電容量應供其有效動作多少小時以上？",{"A":16,"B":17,"C":18,"D":19},"0.5","1","1.5","2","D",null,[],false,"本題考點：《各類場所消防安全設備設置標準》第 192-1 條所定防災監控系統綜合操作裝置之緊急電源供電容量。\n【正解理由】第 192-1 條第二項明定「防災監控系統綜合操作裝置之緊急電源準用第三十八條規定，且其供電容量應供其有效動作二小時以上」；準用第 38 條者為緊急電源之種類（發電機設備或蓄電池設備），供電時數則由本條另行寫明為二小時以上，故選 D。\n【逐項排除】\n(A) 0.5 小時即三十分鐘，為第 38 條就室內消防栓設備緊急電源所定之供電容量；第 192-1 條準用該條僅及於電源種類，時數另有規定，本項錯誤。\n(B) 1 小時為第 95 條就全區及局部放射方式緊急電源所定之容量，非本裝置之規定，本項錯誤。\n(C) 1.5 小時未見於第 192-1 條，亦非其所準用之第 38 條所定時數，本項錯誤。\n(D) 二小時與第 192-1 條第二項「供其有效動作二小時以上」相符，為本題正解。\n【記憶點】防災監控系統綜合操作裝置：電源種類看第 38 條，供電時數看第 192-1 條的二小時。","防災監控系統綜合操作裝置是《設置標準》第 11 條所列消防搶救上之必要設備之一，於 110 年 6 月 25 日修正時以第 30-1 條與第 192-1 條成套增訂。應設場所依第 30-1 條為：高層建築物、總樓地板面積在五萬平方公尺以上之建築物、總樓地板面積在一千平方公尺以上之地下建築物，以及其他經中央主管機關公告之供公眾使用之場所。設置位置與監控範圍依第 192-1 條第一項，應設置於防災中心、中央管理室或值日室等經常有人之處所，並監控或操作火警自動警報設備之受信總機、瓦斯漏氣火警自動警報設備之受信總機、緊急廣播設備之擴大機及操作裝置、連結送水管之加壓送水裝置及與其送水口處之通話連絡、緊急發電機、常開式防火門之偵煙型探測器、室內消防栓與自動撒水及泡沫與水霧等滅火設備加壓送水裝置、乾粉與惰性氣體及鹵化烴等滅火設備、排煙設備共九款。緊急電源要求二小時，與它在災時的角色相稱：個別設備只需撐過自身動作所需時間，而綜合操作裝置必須在整個搶救期間持續提供監控與操作能力，因此本條在準用第 38 條的電源種類之外，另把供電容量明文寫死。命題常見的變化，是把應設場所的五萬平方公尺與一千平方公尺互換，或把「準用第三十八條規定」誤讀成連時數一併準用；讀條文時要看清楚，準用句與「且其供電容量應供其有效動作二小時以上」是兩段並列的要求。另可一併記第 189 條特別安全梯或緊急昇降機間排煙室之排煙設備，其排煙口、進風口、排煙機及進風機連接緊急電源，供電容量應供其有效動作三十分鐘以上。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-fire-law-015","某一百貨商場為地上八層、地下三層，總樓地板面積 3 千平方公尺。其火警自動警報設備之鳴動方式何者錯誤？",15,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-fire-law-017","下列那一處公共危險物品之場所屬於一般滅火困難場所？",17,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-fire-law-014","下列那一場所不是應設置無線電通信輔助設備之場所？",14,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-fire-law-018","下列何者非經中央主管建築機關認定符合耐燃一級之「不因火熱引起燃燒、熔化、破裂變形及產生有害氣體」之材料？",18,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-fire-law-013","某建築物設置收納金屬製避難梯為避難器具，其升降口之施工方法何者錯誤？",13,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-fire-law-019","依各類場所消防安全設備設置標準第 12 條之場所用途分類，下列何者錯誤？",19,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-fire-law-016",110,"依公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法規定，有關六類公共危險物品之分類，下列敘述何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-fire-law-016",109,"依公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法之規定，一般瓦斯行存放多少公斤以上液化石油氣，應設置漏氣警報器？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-fire-law-016",108,"依據各類場所消防安全設備設置標準，防災中心之位置與構造，下列規定何者錯誤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-fire-law-016",107,"依各類場所消防安全設備檢修及申報作業基準之規定，進行二氧化碳滅火設備音響警報檢查判定的標準，是一防護區域或防護對象物之警報系統應正確，且距警報裝置 1 公尺處之音量應在多少分貝以上？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-fire-law-016",106,"依據建築技術規則建築設計施工編規定，下列何者屬耐火板？",1785123157415]