[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-fire-law-018":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-消防法規概要-018","fire-111-1-fire-law-018",111,1,18,"下列何者非經中央主管建築機關認定符合耐燃一級之「不因火熱引起燃燒、熔化、破裂變形及產生有害氣體」之材料？",{"A":16,"B":17,"C":18,"D":19},"空心磚","玻璃纖維","陶瓷品","石膏板","D",null,[],false,"本題考點：建築技術規則就「不燃材料」所為之定義列舉，以及石膏板之耐燃等級歸屬。\n【正解理由】建築技術規則建築設計施工編第 1 條第 28 款所稱不燃材料，指「混凝土、磚或空心磚、瓦、石料、鋼鐵、鋁、玻璃、玻璃纖維、礦棉、陶瓷品、砂漿、石灰及其他經中央主管建築機關認定符合耐燃一級之不因火熱引起燃燒、熔化、破裂變形及產生有害氣體之材料」；石膏板不在該列舉之內，而係同條第 30 款耐燃材料（耐燃三級）所列者，故選 D。\n【逐項排除】\n(A) 空心磚為第 28 款明列之不燃材料，符合耐燃一級。\n(B) 玻璃纖維同列於第 28 款之不燃材料，符合耐燃一級。\n(C) 陶瓷品同列於第 28 款之不燃材料，符合耐燃一級。\n(D) 石膏板列於第 30 款耐燃材料，屬耐燃三級，非耐燃一級，為本題應選者；須與第 29 款耐火板（耐燃二級）所列之「耐燃石膏板」分辨清楚。\n【記憶點】耐燃一級叫不燃材料、二級叫耐火板、三級叫耐燃材料；石膏板在三級，耐燃石膏板才在二級。","建築技術規則把材料的耐火表現分成三個等級，並各給一個法定名稱：不燃材料對應耐燃一級，耐火板對應耐燃二級，耐燃材料對應耐燃三級。第 1 條第 28 款的不燃材料以列舉加概括方式定義，列舉者為混凝土、磚或空心磚、瓦、石料、鋼鐵、鋁、玻璃、玻璃纖維、礦棉、陶瓷品、砂漿、石灰，概括者為其他經中央主管建築機關認定符合耐燃一級之材料；第 29 款耐火板列舉木絲水泥板、耐燃石膏板；第 30 款耐燃材料列舉耐燃合板、耐燃纖維板、耐燃塑膠板、石膏板。石膏板與耐燃石膏板只差兩字卻分屬不同等級，正是本題設陷阱之處。這組定義之所以是消防法規的必考基礎，在於《設置標準》多處以耐燃一級材料裝修作為放寬或免設之要件：第 188 條第一款但書規定戲院、電影院、歌廳、集會堂等場所觀眾席，及工廠等類似建築物，其天花板高度在五公尺以上，且天花板及室內牆面以耐燃一級材料裝修者，得不受每層樓地板面積每五百平方公尺內以防煙壁區劃之限制；第 190 條所列得免設排煙設備之處所，多款均要求天花板及室內牆面以耐燃一級材料裝修，並就防火門窗等防火設備附加半小時或一小時以上阻熱性之要求，其第一款就第十層以下各樓層之非居室部分，另給樓地板面積每一百平方公尺以下以防煙壁區劃之替代路徑，兩目擇一即可；第 159 條第五款第二目就長期照顧服務機構等場所免設避難器具之要件，亦明定裝修材料以耐燃一級材料裝修。因此判斷某材料是否屬耐燃一級，會直接影響一棟建築物要不要設排煙設備或避難器具，不只是名詞題。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-fire-law-017","下列那一處公共危險物品之場所屬於一般滅火困難場所？",17,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-fire-law-019","依各類場所消防安全設備設置標準第 12 條之場所用途分類，下列何者錯誤？",19,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-fire-law-016","防災監控系統綜合操作裝置之緊急電源供電容量應供其有效動作多少小時以上？",16,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-fire-law-020","依消防法規定，下列敘述何者正確？",20,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-fire-law-015","某一百貨商場為地上八層、地下三層，總樓地板面積 3 千平方公尺。其火警自動警報設備之鳴動方式何者錯誤？",15,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-fire-law-021","依建築技術規則建築設計施工編所訂之建築技術用語，下列何者錯誤？",21,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-fire-law-018",110,"第一種室內消防栓與室外消防栓之比較，下列敘述何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-fire-law-018",109,"有一固態酒精儲槽水平剖面半徑為 10 公尺，依防火牆及防火水幕設置基準，其假想火面高度應為多少公尺？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-fire-law-018",108,"依消防法參加義勇消防編組之人員接受訓練、演習、服勤期間，其所屬機關（構）、學校、團體、公司、廠場應給予何種假別？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-fire-law-018",107,"依各類場所消防安全設備檢修及申報作業基準之規定，供第四類公共危險物品之顯著滅火困難場所之冷卻撒水設備的加壓送水裝置，除非設有保壓措施，否則，啟動後 a 分鐘內應能有效撒水，且加壓送水裝置距撒水區域在 b 公尺以下。a、b 各為何值？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-fire-law-018",106,"依據公共危險物品及可燃性高壓氣體設置標準暨安全管理辦法規定，可燃性高壓氣體儲存場所設有防爆牆或同等以上防護性能者，倘其儲存面積未達多少平方公尺時，其與第一類保護物及第二類保護物安全距離得縮減為零？",1785123157448]