[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-fire-law-024":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-消防法規概要-024","fire-111-1-fire-law-024",111,1,24,"某室外儲槽場所儲槽儲存第四類公共危險物品，儲槽容量合計為 25 萬公秉，防液堤高度應在多少公尺以上？",{"A":16,"B":17,"C":18,"D":19},"0.5","1","1.5","2","B",null,[],false,"本題考點：《公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法》第 38 條 室外儲槽場所儲存第四類公共危險物品時，防液堤高度之本文與但書。\n【正解理由】依該辦法第 38 條第 1 項第 2 款：「防液堤之高度應在五十公分以上。但儲槽容量合計超過二十萬公秉者，高度應在一公尺以上。」本題儲槽容量合計為 25 萬公秉，已超過但書所定之二十萬公秉，故不適用本文之五十公分，而應適用但書之一公尺以上，故選 B。\n【逐項排除】\n(A) 0.5 公尺是第 38 條第 1 項第 2 款本文之值（五十公分以上），適用於儲槽容量合計未超過二十萬公秉之情形，本題容量已達 25 萬公秉，不適用。\n(B) 1 公尺即該款但書所定之高度，與本題容量合計超過二十萬公秉之條件相符，為正確答案。\n(C) 1.5 公尺：第 38 條 就防液堤高度並無此值。\n(D) 2 公尺：同上，該條亦未定二公尺之防液堤高度。\n【記憶點】防液堤高度五十公分起算，儲槽容量合計超過二十萬公秉者改為一公尺。","防液堤的作用是把儲槽洩漏的液體侷限在一個可控範圍內，因此第 38 條第 1 項是圍繞「容量、面積、座數、動線」四件事展開。容量方面，單座儲槽周圍防液堤之容量應為該儲槽容量百分之一百十以上；同一地區設有二座以上儲槽者，應為最大儲槽容量百分之一百十以上。面積與座數方面，防液堤內面積不得超過八萬平方公尺；堤內設置儲槽不得超過十座，但其儲槽容量均在二百公秉以下，且所儲存物之閃火點在攝氏七十度以上未達二百度者，得設置二十座以下，儲存物之閃火點在攝氏二百度以上者則無設置數量之限制。動線方面，防液堤周圍應設道路並與區內道路連接，道路寬度不得小於六公尺，僅在堤內儲槽容量均在二百公秉以下、儲存物閃火點均在攝氏二百度以上，或周圍設置道路確有困難，且設有足供消防車輛迴車用之場地時，其設置之道路得為二面以上。\n幾何條件也常入題：室外儲槽之直徑未達十五公尺者，防液堤與儲槽側板外壁間之距離不得小於儲槽高度之三分之一；其為十五公尺以上者，不得小於儲槽高度之二分之一。與本題高度數值容易混淆的是分隔堤：同項第 8 款規定儲槽容量超過一萬公秉者，應在各個儲槽周圍設置分隔堤，分隔堤高度應在三十公分以上，且至少低於防液堤二十公分。兩組數字並列來記，防液堤是五十公分／一公尺，分隔堤是三十公分且低於防液堤二十公分。\n另有兩個以容量分界的附加規定：容量在一萬公秉以上者，防液堤應設置洩漏檢測設備，並於可進行處置處所設置警報設備；高度一公尺以上之防液堤，每間隔三十公尺應設置出入防液堤之階梯或土質坡道。第 38 條第 2 項並就儲存第四類以外液體六類物品之儲槽另定：其防液堤容量不得小於最大儲槽容量，也就是一百而非一百一十，且僅準用第二款、第七款至第十二款及第十四款。\n相關考點可連到第 37 條 室外儲槽場所的保留空地與相鄰儲槽間距，以及第 40 條 儲存烷基鋁、烷基鋰、乙醛、環氧丙烷者應設惰性氣體封阻設備、洩漏侷限設施與冷卻或保冷裝置；設備面則有《各類場所消防安全設備設置標準》第 216 條 冷卻撒水設備，撒水量按槽壁總防護面積每平方公尺每分鐘二公升以上計算，水源容量在最大一座儲槽連續放水四小時之水量以上。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-fire-law-023","消防安全設備檢修專業機構於證書有效期間內，進行證書記載事項變更時，檢修機構應自事實發生之日起多久期間內，依收費標準繳納證書費，並檢具申請書及變更事項證明文件，向中央主管機關申請換發證書？",23,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-fire-law-025","依公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法，有關六類公共危險物品之販賣場所及其位置、構造及設備等規定，下列敘述何者正確？",25,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-fire-law-022","有關山林、田野引火燃燒申請及防火管理作為，下列敘述何者錯誤？",22,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-fire-law-026","依公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法之規定，液化石油氣備用量，供營業使用者，不得超過 X 公斤；供家庭使用者，不得超過 Y 公斤，下列敘述何者正確？",26,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-fire-law-021","依建築技術規則建築設計施工編所訂之建築技術用語，下列何者錯誤？",21,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-fire-law-027","依公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法之規定，儲存第五類公共危險物品分級屬 A 型，其儲存量達管制量 5 倍以上未達 10 倍者且周圍設有圍牆之室內儲存場所，其應保留空地寬度應為多少公尺以上？",27,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-fire-law-024",110,"依各類場所消防安全設備設置標準規定，有關連結送水管之送水設計壓力規定計算，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-fire-law-024",109,"依各類場所消防安全設備設置標準之規定，有一容納超過 300 人老人福利機構餐廳，其樓地板面積在多少平方公尺以上，廚房排油煙管及煙罩即應裝設簡易自動滅火裝置？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-fire-law-024",108,"依消防法第 6 條及其相關規定，有關住宅用火災警報器下列何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-fire-law-024",107,"消防法所稱消防防護計畫應包括之事項，下列何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-fire-law-024",106,"下列有關消防安全設備檢修專業機構管理辦法規定之敘述，何者錯誤？",1785123157531]