[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-fire-law-031":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-消防法規概要-031","fire-111-1-fire-law-031",111,1,31,"依消防安全設備及必要檢修項目檢修基準規定，使用加熱試驗器分別對差動式局限型 1 種探測器及離子式局限型光電式局限型 2 種探測器加熱，確認其應動作之時間分別是 A 秒內及 B 秒內，A+B 為多少？",{"A":16,"B":17,"C":18,"D":19},"90","100","120","150","A",null,[],false,"本題考點：《消防安全設備及必要檢修項目檢修基準》火警自動警報設備性能檢查中，各型探測器受試驗器作用後應動作之時間表。\n【正解理由】依該基準第十三章火警自動警報設備之性能檢查，感熱式探測器動作時間表列「差動式局限型：一種三十秒、二種三十秒」；偵煙式探測器動作時間表列「離子式局限型、光電式局限型：一種三十秒、二種六十秒、三種九十秒」。題幹之 A 為差動式局限型一種，即三十秒；B 為離子式局限型、光電式局限型二種，即六十秒；A＋B＝三十秒＋六十秒＝九十秒，故選 A。\n【逐項排除】\n(A) 30＋60＝90 秒，與表列兩格數值完全相符，為本題應選者。\n(B) 100 秒：兩表之時間格分別為 30、40、60、90、120 秒，任取兩格相加均無從得出 100 秒。\n(C) 120 秒：係把偵煙式二種誤記為三種之 90 秒而得（30＋90），或誤取定溫式局限型二種之 120 秒單獨作答。\n(D) 150 秒：係誤將定溫式局限型二種之 120 秒與差動式局限型之 30 秒相加，兩者均非題幹所問之探測器種別。\n【記憶點】差動式局限型不分一、二種都是三十秒；偵煙式局限型一、二、三種依序三十、六十、九十秒。","檢修基準對探測器之性能檢查，是以「試驗器種類×探測器種別」決定應動作時間：感熱型用加熱試驗器、偵煙式用加煙試驗器、火焰式則以動作試驗器之紅外線或紫外線照射。感熱式時間表列差動式局限型與補償式局限型之一種、二種均為三十秒；定溫式局限型則為特種四十秒、一種六十秒、二種一百二十秒——定溫式須蓄熱至標稱動作溫度才會動作，容許時間自然拉長，這是感熱型內部最容易互相張冠李戴的一組。偵煙式時間表列離子式局限型與光電式局限型一種三十秒、二種六十秒、三種九十秒，種別數字愈大、靈敏度愈低、容許時間愈長，呈三十秒等差排列，是本題最好用的記憶規律。\n另一組常被合併命題的是蓄積性能：對感熱式探測器加熱時，應在表列時間加上蓄積式中繼器或受信總機所設定蓄積時間之合計時間內動作，該合計時間最大二十秒；偵煙式非蓄積型為表列時間加蓄積時間之合計（最大六十秒），蓄積型再加上標稱蓄積時間並多五秒；火焰式則為三十秒加蓄積時間（最大二十秒）。此外，對蓄積式受信總機作火災表示試驗時，實測之蓄積時間應在受信總機設定時間加五秒以內。題幹有沒有出現「蓄積」二字，就是要不要加算的判斷點。\n延伸考點方面，《各類場所消防安全設備設置標準》第一百十四條依裝置場所高度限定可用之探測器種類，十五公尺以上未滿二十公尺者僅離子式局限型一種、光電式局限型一種、光電式分離型一種及火焰式可用；第一百二十條則訂有有效探測範圍表，防火構造建築物、裝置面未滿四公尺時，差動式局限型一種為九十平方公尺、二種為七十平方公尺，定溫式局限型二種僅二十平方公尺。設置面與檢修面兩套數值常在同一年度分開命題，宜對照記憶。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-fire-law-030","依各類場所消防安全設備設置標準規定，某樓層高度超過 10 公尺且樓地板面積在 700 平方公尺以上之高架儲存倉庫，其撒水頭設置應符合之規定，下列敘述何者正確？",30,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-fire-law-032","供某住宿式長期照顧機構使用之五層樓建築物，各樓層若符合下列何者之規定，得免設避難器具？",32,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-fire-law-029","依各類場所消防安全設備設置標準規定，下列何場所之樓地板面積合計未達 1 千平方公尺，得設置水道連結型自動撒水設備或與現行法令同等以上效能之滅火設備？①產後護理之家 ②團體家屋 ③精神護理之家 ④兒童及少年福利機構",29,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-fire-law-033","依消防法施行細則規定，供公眾使用建築物應遴選防火管理人並制定消防防護計畫，其相關規定下列何者錯誤？",33,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-fire-law-028","可燃性高壓氣體儲存場所防爆牆，其鋼筋混凝土經過 28 日養生後之抗壓強度（kgf\u002Fcm2），應為多少以上？",28,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-fire-law-034","依消防安全設備及必要檢修項目檢修基準規定，對二氧化碳滅火器進行重量檢查時，如失重超過多少比例以上或壓力表示值在綠色範圍外時，應予以更新，下列何者正確？",34,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-fire-law-031",110,"有關標示設備之規定，下列敘述何者正確？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-fire-law-031",109,"依各類場所消防安全設備設置標準，有關泡沫原液儲存量、泡沫原液與水混合使用濃度之規定，下列敘述何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-fire-law-031",108,"依消防機關辦理建築物消防安全設備審查及查驗作業基準規定，消防安全設備圖說審查及竣工查驗之期限，以受理案件後Ｘ至Ｙ日內結案為原則。但供公眾使用建築物或構造複雜者，得視需要延長，並通知申請人，最長不得超過Ｚ日，請問下列何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-fire-law-031",107,"依各類場所消防安全設備設置標準之規定，有關緊急電源插座，下列敘述何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-fire-law-031",106,"下列有關消防法施行細則第 15 條自衛消防編組規定之敘述，何者正確？",1785123157604]