[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-fire-law-034":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-消防法規概要-034","fire-111-1-fire-law-034",111,1,34,"依消防安全設備及必要檢修項目檢修基準規定，對二氧化碳滅火器進行重量檢查時，如失重超過多少比例以上或壓力表示值在綠色範圍外時，應予以更新，下列何者正確？",{"A":16,"B":17,"C":18,"D":19},"5%","7%","10%","14%","C",null,[],false,"本題考點：《消防安全設備及必要檢修項目檢修基準》滅火器性能檢查中，二氧化碳滅火器重量檢查之汰換判定值。\n【正解理由】依該基準第一章滅火器三、性能檢查，蓄壓式滅火器檢查順序之注意事項明定：「對二氧化碳滅火器及海龍滅火器進行重量檢查時，如失重超過 10％以上或壓力表示值在綠色範圍外時，應予以更新。」題幹所問即此判定值，失重門檻為百分之十，故選 C。\n【逐項排除】\n(A) 5%：非該基準就重量檢查所定之汰換門檻；滅火藥劑量之判定另以總重量容許範圍表之公克數表示，並非百分比。\n(B) 7%：亦非基準所列數值，與正解僅差三個百分點，屬典型干擾選項。\n(C) 10%：與原文「失重超過 10％以上或壓力表示值在綠色範圍外時，應予以更新」相符，且適用對象為二氧化碳滅火器及海龍滅火器二者，為本題應選者。\n(D) 14%：非基準所列數值；該基準中與百分比有關者為新更換充填之滅火藥劑，充填完成時噴射性能須達所充填量之 90% 以上、使用期限內須達 80% 以上，以及二氧化碳純度應為 99% 以上，均與重量檢查無涉。\n【記憶點】二氧化碳與海龍滅火器秤重，失重逾一成或壓力表示值不在綠色範圍，就要更新。","滅火器的檢修分外觀檢查與性能檢查兩層。外觀檢查以目視及手感確認本體容器、安全插梢、壓把、護蓋、皮管、噴嘴與喇叭噴管、壓力指示計、壓力調整器、安全閥、保持裝置、車輪與氣體導入管等，其中壓力指示值應在綠色範圍內；本體容器若熔接部位受損、顯著變形、顯著腐蝕或鐵鏽剝離，得不再施以性能檢查即予汰換。性能檢查則依加壓方式分為化學反應式、加壓式與蓄壓式三種順序，二氧化碳滅火器與海龍滅火器因內壓高，蓄壓式的排氣步驟特別將其排除，改以秤重與壓力表示值判定，本題的百分之十失重規定就是安放在這個位置。\n與此呼應的是第一章一、一般注意事項所定的權責分工：除二氧化碳及鹵化物滅火器之重量檢查或確認壓力指示計指針位置等性能檢查外，各類型滅火器之性能檢查（包括藥劑更換充填、加壓用氣體容器之氣體充填等不良狀況處置）應由專業廠商專任之消防專技人員為之。換言之，二氧化碳與鹵化物滅火器的秤重與看壓力表，體例上被視為相對單純的項目，這也解釋了為什麼它們的判定值會用一個好記的百分比來定。\n容易混淆的數值有三組，宜整理成表：其一是滅火藥劑量之總重量容許範圍，以標示重量分級給公克數，例如一公斤未滿為＋100g 至－80g、一公斤以上二公斤未滿為＋200g 至－80g、二公斤以上五公斤未滿為＋300g 至－100g，級距一路擴大到一百公斤以上之＋2,400g 至－1,000g；其二是噴射性能之 90% 與 80%，以及二氧化碳純度 99%；其三是性能檢查完成後之標示與檢修環制度——標示須依格式張貼且不得覆蓋原出廠標示，檢修環材質為一體成型之硬質無縫塑膠、壓克力或鐵環，顏色以紅、橙、黃、綠、藍交替更換，自一百一十年度起為紅色，一百一十一年度橙色、一百一十二年度黃色、一百一十三年度綠色、一百一十四年度藍色，依此類推。看到題目出現百分比就先問：問的是失重、噴射性能，還是純度。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-fire-law-033","依消防法施行細則規定，供公眾使用建築物應遴選防火管理人並制定消防防護計畫，其相關規定下列何者錯誤？",33,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-fire-law-035","某合法 KTV 視聽歌唱場所經當地消防機關會勘通過依法取得室內裝修許可，依照消防安全設備檢修及申報辦法規定，自該室內裝修許可核發之日期起算，距申報期限在多少個月以內，免辦理當次檢修及申報備查？",35,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-fire-law-032","供某住宿式長期照顧機構使用之五層樓建築物，各樓層若符合下列何者之規定，得免設避難器具？",32,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-fire-law-036","受託辦理檢修之檢修機構應依相關規定檢修完成消防安全設備後，依照消防安全設備檢修及申報辦法規定，應附加檢修完成標示檢修機構專業樣式以何種顏色為底？",36,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-fire-law-031","依消防安全設備及必要檢修項目檢修基準規定，使用加熱試驗器分別對差動式局限型 1 種探測器及離子式局限型光電式局限型 2 種探測器加熱，確認其應動作之時間分別是 A 秒內及 B 秒內，A+B 為多少？",31,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-fire-law-037","依據乾粉滅火設備各種標示規格規定，其標示規格為長 480 mm 以上，寬 270 mm 以上，黃底黑字，每字大小為 25 mm×25 mm 以上，係屬下列何者？",37,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-fire-law-034",110,"依消防安全設備及必要檢修項目檢修基準規定，室內消防栓設備水帶製造年份超過 10 年應使用耐水壓試驗機，施以 X kgf\u002Fcm2 以上水壓試驗 Y 分鐘合格，始得繼續使用。X＋Y 為多少？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-fire-law-034",109,"依消防幫浦加壓送水裝置等及配管摩擦損失計算基準，有關幫浦性能之規定，幫浦所消耗之動力，在額定出水量 150%時，其軸動力不得超過馬達額定輸出馬力之多少以下？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-fire-law-034",108,"依消防法施行細則，有關消防安全設備之設計、監造、裝置及檢修工作項目之規定，下列何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-fire-law-034",107,"依各類場所消防安全設備設置標準之規定，下列何者非屬甲類場所？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-fire-law-034",106,"各類場所之管理權人應委託檢修專業機構或消防法第 7 條規定之人員辦理檢修，並於檢修完成後幾日內，向當地消防機關申報？",1785123157629]