[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-fire-science-025":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"火災學概要","fire-science","火災學 · Fire Science","火災學",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-火災學概要-025","fire-111-1-fire-science-025",111,1,25,"近來消防機關大力推行安裝住宅用火災警報器，其安裝位置在天花板或牆壁上緣，主要考量因素為何？",{"A":16,"B":17,"C":18,"D":19},"起火空間的火載量","天花板噴射流的溫度與速度","持續燃燒時間","輻射回饋效應","B",null,[],false,"本題考點：天花板噴射流的形成，及其與火災探測、住宅用火災警報器裝設位置的關係。\n【正解理由】火源上方形成浮力火羽流，撞到天花板後無法繼續上升，轉為沿天花板向四周徑向擴散的高溫薄層氣流，稱天花板噴射流。這一層是室內最早出現高溫與煙粒子、且流速最快的位置，感知元件必須置於此層之內才能在火災初期動作；因此住宅用火災警報器裝在天花板面，或裝在牆壁上緣接近天花板之處，主要考量正是天花板噴射流的溫度與速度，故選 B。\n【逐項排除】\n(A) 起火空間的火載量決定火災能持續多久與總放熱量，屬火災規模的描述，與警報器該裝在哪個高度沒有因果關係。\n(B) 天花板噴射流的溫度與速度直接決定警報器能否及早感知，是裝設高度的決定性依據，敘述正確。\n(C) 持續燃燒時間同樣是火災延時的描述，警報器的任務是在初期發報，不是撐完整場火災，與裝設位置無涉。\n(D) 輻射回饋效應是熱煙層與火焰把熱回輻射到燃料表面而加速燃燒，屬火勢成長機制，不是決定警報器裝設高度的因素。\n【記憶點】警報器要泡在天花板噴射流裡才會早響。","天花板噴射流是火災探測理論的核心概念。火源上方的浮力羽流上升撞到天花板後無法繼續上升，轉為沿天花板向四周徑向流動，形成一層厚度大約只有天花板高度百分之十上下的高溫薄層，層內的最高溫度與最大流速出現在靠近天花板表面處，離開這一層往下，溫度與流速都迅速衰減。探測器與撒水頭之所以一律裝在天花板面或其鄰近範圍，就是要讓感知元件浸在這層流體裡；裝得太低，動作時間會明顯延後。\n同一理論也解釋了兩個常考的裝設細節。其一是天花板與牆面的交角處存在空氣滯留區，該處氣流幾乎不流動，煙與熱不易到達，因此裝在牆面時必須避開緊貼天花板的死角，需離開一段距離。其二是不宜設在空調出風口附近，強制氣流會把煙吹散、稀釋，使感知延遲。\n住宅用火災警報器與建築物內的火警自動警報設備在原理上共用這套概念，差別在前者是電池式單體裝置、偵知後由自身發出警報音，後者是探測器連接受信總機的系統。住宅火災的死亡多發生在深夜睡眠時段，及早發出足以喚醒住戶的警報是其設計目的，所以裝設位置要選在煙最早抵達且濃度足夠之處。\n易混淆對照：偵煙式反應的是煙粒子濃度，能在陰燃階段即動作；定溫式與差動式反應的是溫度與溫升速率，動作較晚但較不易受水蒸氣、油煙誤報，廚房一類場所才會改用溫感型式。相關考點連結：探測器裝置高度分級與各型式的適用場所、火羽流與天花板噴射流的溫度衰減關係，以及動作時間與火災成長速率的比較。\n另可一併記憶：感知元件的動作時間受火災成長速率、天花板高度與元件本身熱時間常數三者共同左右。天花板愈高，火羽流上升途中捲入的冷空氣愈多，抵達天花板時溫度已被稀釋，天花板噴射流也隨半徑增加而快速降溫，離火源愈遠的位置動作愈慢，這正是挑高空間難以單靠天花板面裝設達成早期偵知的原因。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-fire-science-024","下列何者非影響建築物中煙霧流動與蔓延的主要因素？",24,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-fire-science-026","一公克水完全汽化成水蒸氣，溫度 327℃水蒸氣體積為 V1，溫度 727℃水蒸氣體積為 V2，則 V2\u002FV1 值？",26,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-fire-science-023","建築物起火後，對於防止火焰由下層窗戶往上層延燒，下列敘述何者錯誤？",23,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-fire-science-027","下列關於乙炔的敘述，何者錯誤？",27,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-fire-science-022","連棟式木造建築物引發火災，消防隊射水同時拆除未受火勢波及的房屋，請問其採取的滅火方法係下列何者？",22,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-fire-science-028","通風控制燃燒下，居室內有可燃物 1200 kg，該居室有一開口面積 6 m2，高度 2 m，則火災持續時間約幾分鐘？",28,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-fire-science-025",110,"請依據可燃性氣體完全燃燒時的化學理論濃度，計算丙烷的燃燒下限？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-fire-science-025",109,"有關火羽流的敘述，下列何者錯誤？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-fire-science-025",108,"木材受熱分解進而燃燒的過程中，當加熱到引火溫度時，可燃性氣體釋出量迅速增加，試問木材的引火溫度約為多少℃？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-fire-science-025",107,"下列何者並非複燃（backdraft）發生之原因？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-fire-science-025",106,"依據實驗，人穿著普通作業服時，其受熱之界限值約為多少？",1785123162058]