[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-111-1-water-chemical-002":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-水與化學系統消防安全設備概要-002","fire-111-1-water-chemical-002",111,1,2,"有關室外消防栓與室內消防栓之瞄子放水壓力之敘述，下列何者正確？",{"A":16,"B":17,"C":18,"D":19},"室外消防栓（一般場所）放水壓力應在 2.5 kgf\u002Fcm2～7 kgf\u002Fcm2","第一種（一般場所）消防栓放水壓力應在 1.7 kgf\u002Fcm2～7 kgf\u002Fcm2","第一種（公共危險物品場所）消防栓放水壓力應在 2.5 kgf\u002Fcm2～7 kgf\u002Fcm2","第二種消防栓放水壓力應在 0.6 kgf\u002Fcm2～7 kgf\u002Fcm2","B",null,[],false,"本題考點：各類消防栓瞄子放水壓力的下限與上限，見《各類場所消防安全設備設置標準》第 34 條、第 37 條與第 209 條。\n【正解理由】依第 34 條第一項第一款第二目，第一種消防栓「各消防栓瞄子放水壓力在每平方公分一點七公斤以上或 0.17MPa 以上」為下限；第 37 條第二項第四款「室內消防栓瞄子放水壓力超過每平方公分七公斤時，應採取有效之減壓措施」為上限。《消防安全設備及必要檢修項目檢修基準》室內消防栓設備綜合檢查之判定方法亦載明放水壓力應在 1.7kgf\u002Fcm2 以上 7kgf\u002Fcm2 以下，故選 B。\n【逐項排除】\n(A) 室外消防栓依第 40 條第二款出水壓力在每平方公分二點五公斤以上，下限雖對，但第 42 條第二項規定超過每平方公分六公斤時即應採減壓措施，上限為 6 而非 7。\n(B) 第一種消防栓下限每平方公分一點七公斤、上限七公斤，與條文及檢修基準判定值一致，為本題應選者。\n(C) 公共危險物品等場所之室內消防栓依第 209 條第一項第四款，放水壓力在每平方公分三點五公斤以上或 0.35MPa 以上，下限並非 2.5。\n(D) 第二種消防栓依第 34 條第一項第二款第二目，放水壓力同為每平方公分一點七公斤以上，下限不是 0.6。\n【記憶點】一般場所第一種、第二種消防栓為 1.7 至 7；室外消防栓為 2.5 至 6；公共危險物品等場所室內消防栓下限 3.5。","放水壓力同時規定下限與上限，是因為兩端各自對應一個要件：下限保障射程與放水量，壓力不足時瞄子射流到不了起火點；上限保障操作安全，壓力過高時水帶反作用力會使人員無法穩定持握。《各類場所消防安全設備設置標準》的體例是「條文本身只寫下限，上限藏在加壓送水裝置的減壓條款裡」——第 34 條寫第一種、第二種消防栓瞄子放水壓力在每平方公分一點七公斤以上或 0.17MPa 以上，上限見第 37 條第二項第四款「室內消防栓瞄子放水壓力超過每平方公分七公斤時，應採取有效之減壓措施」；室外消防栓的下限在第 40 條第二款（每平方公分二點五公斤以上或 0.25 MPa 以上），上限見第 42 條第二項（超過每平方公分六公斤或 0.6Mpa 時應減壓）。公共危險物品等場所另成一套：第 209 條第一項第四款室內消防栓為每平方公分三點五公斤以上、放水量每分鐘二百六十公升以上；第 210 條第一項第二款則寫室外消防栓瞄子放水壓力超過每平方公分七公斤或 0.7MPa 時應減壓。\n單位換算是本題型的隱藏考點：1 kgf\u002Fcm² 約為 0.098 MPa，也約當 10 公尺水頭。因此 1.7 kgf\u002Fcm² ＝ 0.17 MPa ≒ 17 公尺水頭，正是第 37 條第一項第三款第二目幫浦全揚程公式尾數 +17m 的由來；室外消防栓 2.5 kgf\u002Fcm² ≒ 25 公尺水頭，對應第 42 條的 +25m。把壓力值與揚程公式尾數綁在一起記，可同時解決兩類題目。\n易混淆對照：瞄子放水量（第一種每分鐘一百三十公升、第二種每分鐘八十公升）與幫浦出水量（第 37 條第一項第三款第一目：第一種每支每分鐘一百五十公升、第二種每支每分鐘九十公升）是兩個不同欄位，後者含配管損失與洩漏裕度。另外，《消防安全設備及必要檢修項目檢修基準》給的是檢修判定值，設置標準給的是設置值與減壓門檻，數字雖一致，性質不同，答題時要看題幹問的是設置規定或檢修判定。",true,[28,31,35,40,44,48],{"webId":29,"stem":30,"number":12,"year":11,"session":12},"fire-111-1-water-chemical-001","依各類場所消防安全設備設置標準規定，下列何種場所不需設置室外消防栓設備？",{"webId":32,"stem":33,"number":34,"year":11,"session":12},"fire-111-1-water-chemical-003","某公共危險物品場所設置室外消防栓設備，在裝置全部消防栓數量 5 支時，其所需之水源容量至少應為多少立方公尺以上？",3,{"webId":36,"stem":37,"number":38,"year":39,"session":12},"fire-110-1-water-chemical-040","依消防安全設備及必要檢修項目檢修基準，冷卻撒水設備之供第四類公共危險物品之顯著滅火困難場所之加壓送水裝置，啟動後 X 分鐘內應能有效撒水，且加壓送水裝置距撒水區域在 Y 公尺以下，但設有保壓措施者不在此限。X、Y 分別為何？",40,110,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-water-chemical-004","裝置於舞臺之開放式自動撒水設備，依規定下列何者正確？",4,{"webId":45,"stem":46,"number":47,"year":39,"session":12},"fire-110-1-water-chemical-039","依消防安全設備及必要檢修項目檢修基準，冷卻撒水設備之遠隔啟動裝置，限用於儲存閃火點多少℃以下公共危險物品之室外儲槽？",39,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-water-chemical-005","有關移動式泡沫滅火設備，依各類場所消防安全設備設置標準之規定，下列敘述何者正確？",5,[53,56,60,64,68],{"webId":54,"year":39,"stem":55,"number":13},"fire-110-1-water-chemical-002","連結送水管之中繼幫浦放水測試時，應從送水口以送水設計壓力送水，並以口徑 21 公厘瞄子在最頂層測試，其放水壓力不得小於 X kgf\u002Fcm2，且放水量不得小於 Y L\u002Fmin。X、Y 分別為何？",{"webId":57,"year":58,"stem":59,"number":13},"fire-109-1-water-chemical-002",109,"某地下一層、地上七層建築物，地下層為室內停車空間，面積 200 平方公尺，一至七層為集合住宅，各層面積 100 平方公尺，有室內安全梯直通地下層，本案是否需設置室內消防栓設備？",{"webId":61,"year":62,"stem":63,"number":13},"fire-108-1-water-chemical-002",108,"自動撒水設備竣工時，應做加壓試驗。但密閉乾式管系應併行空氣壓試驗，試驗時，應使空氣壓力達到 X MPa 之標準，其壓力持續 Y 小時，漏氣減壓量應在 Z MPa 以下為合格。X、Y、Z 分別為何？",{"webId":65,"year":66,"stem":67,"number":13},"fire-107-1-water-chemical-002",107,"有關連結送水管之送水口設置規定，下列何者錯誤？",{"webId":69,"year":70,"stem":71,"number":13},"fire-106-1-water-chemical-002",106,"依各類場所消防安全設備設置標準，下列何種場所不需設置滅火器？",1785123166088]