[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-water-chemical-009":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-水與化學系統消防安全設備概要-009","fire-111-1-water-chemical-009",111,1,9,"泡沫滅火設備之減水警報裝置進行性能檢查時，當呼水槽水量減少到多少時，應發出警報？",{"A":16,"B":17,"C":18,"D":19},"1\u002F2","1\u002F3","1\u002F4","1\u002F5","A",null,[],false,"本題考點：《消防安全設備及必要檢修項目檢修基準》泡沫滅火設備性能檢查中，呼水裝置之減水警報裝置判定值。\n【正解理由】依檢修基準泡沫滅火設備性能檢查「呼水裝置」項下之減水警報裝置，檢查方法為關閉補給水閥，再打開排水閥，確認減水警報功能是否正常；其判定方法逐字載明「應無變形、損傷、顯著腐蝕等」及「當呼水槽水量減少到一半時，應發出警報」。一半即二分之一，與選項 (A) 相符，故選 A。\n【逐項排除】\n(A) 1\u002F2 即判定方法所稱「一半」，與泡沫滅火設備性能檢查呼水裝置之減水警報裝置判定值相符，為本題應選者。\n(B) 1\u002F3：檢修基準各章呼水裝置之減水警報判定方法均未出現三分之一之比例。\n(C) 1\u002F4：亦非減水警報之判定比例；四分之一出現在泡沫綜合檢查的 25％還原時間，屬不同項目，勿混用。\n(D) 1\u002F5：檢修基準呼水裝置判定方法未列此比例，以五分之一判定將使警報過遲。\n【記憶點】呼水槽減水警報一律抓「一半」；底閥則看呼水漏斗能否連續溢水、漏斗的水有無減少。","呼水裝置是消防幫浦採吸水揚程配置（水源液面低於幫浦中心）時的必要配件：幫浦停機期間若吸水管內的水回落，再啟動時會因空轉而吸不上水，因此在幫浦上方設呼水槽，經呼水管持續使吸水管與幫浦本體充滿水。呼水槽水量若減少，代表底閥漏水、吸水管洩漏或呼水管制水閥誤關，屬於「幫浦啟動不了」的前兆，所以減水警報裝置是性能檢查的重點項目。\n檢修基準泡沫滅火設備性能檢查的呼水裝置分四個子項。閥類：用手實地操作確認開、關動作是否容易進行。自動給水裝置：確認有無變形、腐蝕等，並打開排水閥檢查自動給水功能是否正常。減水警報裝置：確認有無變形、腐蝕等，關閉補給水閥再打開排水閥，確認減水警報功能是否正常。底閥：拉上吸水管或檢查用鍊條，確認有無異物附著或阻塞；打開幫浦本體上之呼水漏斗的制水閥，確認有無從漏斗連續溢水出來；再關閉呼水管之制水閥，確認底閥之逆止效果是否正常。對應的判定方法為：閥類開關操作應能容易進行；自動給水裝置應無變形、損傷、顯著腐蝕，且當呼水槽水量減少時應能自動給水；減水警報裝置應無變形、損傷、顯著腐蝕，且當呼水槽水量減少到一半時應發出警報；底閥應無異物附著、阻塞等吸水障礙，呼水漏斗應能連續溢水出來，且漏斗的水應無減少。\n跨章一致性可作為記憶依據：水霧滅火設備、冷卻撒水設備各章寫「當呼水槽水量減少到一半時，應發出警報」，室外消防栓設備、射水設備、連結送水管各章寫「當水量減少到二分之一時應發出警報」，自動撒水設備寫「當水量減少到一半時應發出警報」，消防專用蓄水池寫「當水量減少至一半前應發出警報」；用語雖有差異，判定值同為二分之一。延伸考點是同章鄰近項目的判定值：自動撒水設備性能檢查另要求自動給水裝置在呼水槽之水量減少到一半時應能自動給水，可與減水警報一併記憶，避免把兩個項目的觸發條件記反。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-water-chemical-008","固定式泡沫滅火設備（低發泡）進行綜合檢查作業時，發泡倍率應在幾倍以上？",8,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-water-chemical-010","樓地板面積 250 平方公尺之變壓器室，依各類場所消防安全設備設置標準規定，可選擇下列何種消防安全設備？①水霧 ②泡沫 ③二氧化碳 ④乾粉",10,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-water-chemical-007","下列有關撒水頭設置之敘述，何者正確？",7,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-water-chemical-011","依各類場所消防安全設備設置標準規定，消防專用蓄水池應設置於消防車能接近至多少公尺範圍內，易於抽取處？",11,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-water-chemical-006","消防幫浦之防止水溫上升用排放裝置，防止水溫上升用之排水管內之流水量，當幫浦在全閉狀態下連續運轉時，不使幫浦內部水溫，升高至攝氏多少度以上？",6,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-water-chemical-012","有關水霧滅火設備，依各類場所消防安全設備設置標準之規定，下列敘述何者正確？",12,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-water-chemical-009",110,"依據密閉式撒水頭認可基準之規定，進行玻璃球之強度試驗時，標示溫度在多少以上者將採用油浴方式進行測試？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-water-chemical-009",109,"進行低發泡水成膜泡沫放射試驗時，其 25%還原時間應在多久時間以上？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-water-chemical-009",108,"有一總機室，設置二氧化碳滅火設備，採全區放射方式，其每立方公尺防護區域所需滅火藥劑量為多少公斤？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-water-chemical-009",107,"某一學校教學大樓每一樓層皆設有第一種室內消防栓 3 具，則其水源容量應為多少立方公尺？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-water-chemical-009",106,"如無額外防止乾粉與加壓氣體分離之措施，乾粉滅火設備之配管任一部分與彎曲部分之距離，至少應為其管徑的多少倍？",1785123166175]