[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-water-chemical-015":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-水與化學系統消防安全設備概要-015","fire-111-1-water-chemical-015",111,1,15,"採用移動式放射方式之乾粉滅火設備，藥劑種類為第四種乾粉時，每一具噴射瞄子所需藥劑放射量為何？",{"A":16,"B":17,"C":18,"D":19},"18 kg\u002Fmin","27 kg\u002Fmin","45 kg\u002Fmin","60 kg\u002Fmin","A",null,[],false,"本題考點：《設置標準》第 111 條移動式乾粉滅火設備，各種乾粉每一具噴射瞄子之每分鐘藥劑放射量。\n【正解理由】依《各類場所消防安全設備設置標準》第 111 條第五款所附之表，每一具噴射瞄子每分鐘放射量為：第一種乾粉 45 公斤、第二種乾粉或第三種乾粉 27 公斤、第四種乾粉 18 公斤。題目所問為第四種乾粉，對應表列 18 kg\u002Fmin，故選 A。\n【逐項排除】\n(A) 正確。18 kg\u002Fmin 即第 111 條第五款表列之第四種乾粉（主成分碳酸氫鉀及尿素化合物）放射量。\n(B) 錯誤。27 kg\u002Fmin 是同表中第二種乾粉或第三種乾粉之放射量，並非第四種。\n(C) 錯誤。45 kg\u002Fmin 是同表中第一種乾粉（主成分碳酸氫鈉）之放射量。\n(D) 錯誤。60 kg\u002Fmin 出自第 96 條第五款，係移動式二氧化碳滅火設備「每一具瞄子之藥劑放射量在溫度攝氏二十度時，應在每分鐘六十公斤以上」，屬不同滅火藥劑之設備規定。\n【記憶點】移動式乾粉放射量：第一種 45、第二種或第三種 27、第四種 18（第 111 條）；移動式二氧化碳為每分鐘 60 公斤（第 96 條）。","移動式放射方式是由人員拉出皮管、持瞄子近距離射藥劑，因此規定重心在「一支瞄子要噴多少」與「拉得出、看得到」。第 111 條除準用第一百零二條第一款、第二款第二目、第三目、第三款、第四款外，另定六項：儲存容器之容器閥能在皮管出口處以手動開關；儲存容器分設於各皮管設置處；儲存容器近旁設紅色標示燈並標明移動式乾粉滅火設備字樣；設於火災時濃煙不易籠罩之場所；每一具噴射瞄子之每分鐘藥劑放射量符合表列（45／27／18）；皮管、噴嘴及管盤符合 CNS 一一一七七之規定。同樣的體例也見於二氧化碳的第 96 條，差別在其標示為移動式二氧化碳滅火設備字樣、放射量為每分鐘六十公斤以上，且要求設於火災時濃煙不易籠罩之處所。\n藥劑種類的數值在乾粉各條中反覆出現，宜整組記憶。第 99 條全區放射方式所需滅火藥劑量表：每立方公尺防護區域所需滅火藥劑量，第一種 0.6、第二種 0.36、第三種 0.36、第四種 0.24 公斤；每平方公尺開口部所需追加滅火藥劑量，第一種 4.5、第二種 2.7、第三種 2.7、第四種 1.8 公斤。第 102 條第一款充填比：第一種乾粉零點八五以上一點四五以下，第二種或第三種乾粉一點零五以上一點七五以下，第四種乾粉一點五以上二點五以下；同條並要求儲存容器置於防護區域外、溫度攝氏四十度以下且溫度變化較少處，不得日光曝曬或雨水淋濕，明顯處標示充填藥劑量、滅火藥劑種類、最高使用壓力（限加壓式）、製造年限及製造廠商。另第 101 條規定供室內停車空間使用之滅火藥劑，以第三種乾粉為限。\n驗收端可對照《消防安全設備測試報告書測試方法及判定要領》乾粉滅火設備之外觀試驗，其判定要領就充填比亦載明第一種 0.85 以上 1.45 以下、第二種或第三種 1.05 以上 1.75 以下、第四種 1.50 以上 2.50 以下，並要求蓄壓式容器內壓在 10 kgf\u002Fcm² 以上者設符合 CNS10848 及 CNS10849 之容器閥。設置標準與判定要領使用同一組數值，是這類數值題的命題來源。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-water-chemical-014","開放式自動撒水設備之自動啟動裝置，感知撒水頭應設在裝置面距樓地板面高度多少公尺以下，且能有效探測火災處？",14,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-water-chemical-016","乾粉滅火設備進行性能檢查時，關於滅火藥劑量之敘述，下列何者正確？",16,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-water-chemical-013","有關自動撒水設備末端查驗閥之敘述，下列何者正確？",13,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-water-chemical-017","惰性氣體滅火設備進行綜合檢查時，採低壓式者進行放射試驗時，其放射試驗所需之藥劑量，為該放射區域所設滅火藥劑量之多少以上？",17,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-water-chemical-012","有關水霧滅火設備，依各類場所消防安全設備設置標準之規定，下列敘述何者正確？",12,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-water-chemical-018","依各類場所消防安全設備設置標準規定，總樓地板面積 100 平方公尺之何種場所應設置滅火器？ ①咖啡廳 ②幼兒園 ③陳列館 ④商場",18,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-water-chemical-015",110,"公共危險物品儲槽設置補助泡沫消防栓之規定，下列敘述何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-water-chemical-015",109,"公共危險物品室外儲槽場所設置射水設備時，測試之放水壓力應在多少以上？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-water-chemical-015",108,"依各類場所消防安全設備檢修及申報作業基準，對蓄壓式二氧化碳滅火器及海龍滅火器進行重量檢查時，如失重超過多少%以上或壓力表示值在綠色範圍外時，應予以更新？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-water-chemical-015",107,"二氧化碳滅火系統進行性能檢查時，音響警報之判定方法為距警報裝置 X 公尺處之音量應在 Y 分貝以上，其中 X、Y 應為下列何者？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-water-chemical-015",106,"某一高度危險工作場所，其建築物外面設有 4 具室外消防栓，則其水源容量至少應為多少？",1785123166238]