[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-water-chemical-023":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-水與化學系統消防安全設備概要-023","fire-111-1-water-chemical-023",111,1,23,"簡易自動滅火設備進行性能檢查時，蓄壓式滅火藥劑儲存容器滅火藥劑量應與標示差異不超過多少？",{"A":16,"B":17,"C":18,"D":19},"3%","5%","10%","15%","A",null,[],false,"本題考點：簡易自動滅火設備性能檢查中,蓄壓式滅火藥劑儲存容器的藥劑量容許差,屬檢修基準的判定值題。\n【正解理由】依《消防安全設備及必要檢修項目檢修基準》第九章簡易自動滅火設備之性能檢查,蓄壓式滅火藥劑儲存容器以台秤測定,先取下裝設在容器閥之容器閥開放裝置、連接管、操作管及容器固定器具,再將儲存容器置於台秤上測定重量計算至小數點第一位,原文明定「藥劑量則為測定值扣除容器閥及容器重量後所得之值;藥劑量應與標示差異不超過 3%」,判定方法並載明其差值應在充填值 3％以下,故選 A。\n【逐項排除】\n(A) 3% 即該章性能檢查所列容許差,且加壓式儲存容器之藥劑量判定同樣是與標示差異不超過 3%。\n(B) 5% 未見於該章的檢查方法或判定方法。\n(C) 10% 是同基準惰性氣體滅火設備性能檢查所列,其藥劑量差值應在充填值 10％以下,設備別不同。\n(D) 15% 在上述各章的判定方法中都沒有出現。\n【記憶點】簡易自動滅火設備藥劑量差 3%,惰性氣體滅火藥劑差 10%,依所屬章節各認各的。","這題背後是一整套秤重法的檢查邏輯。第九章對蓄壓式與加壓式儲存容器都採台秤測定:取下容器閥開放裝置、連接管、操作管與容器固定器具後,把儲存容器放上台秤,測定值扣除容器閥及容器重量即為藥劑量;注意事項要求測量後將容器號碼、充填量記載於重量表與檢查表上,藥劑量或容器內壓減少時應迅即調查並採取必要措施。加壓式另可用量尺自充填口量測滅火藥劑液面高度,液面高度應與標示高度差異在誤差範圍內。加壓用氣體容器則另有數字:以手旋轉取下後置於計量器測總重量,總重量應比標示重量不少於 14.2 公克;啟動用氣體容器以彈簧秤或秤重計測量,重量不得小於容器上記載之最小重量。\n外觀檢查是另一組常考點:儲存容器與固定架應無變形、損傷、明顯腐蝕、生銹或塗裝剝離,以推押容器方式確認確實固定,周圍溫度須在 40℃ 以下,壓力表指針應在綠色指示範圍內,容器閥開放裝置應裝設安全栓或安全插梢。設置面對照《設置標準》第 111-1 條:應視排油煙管之斷面積、警戒長度及風速配置感知元件及噴頭,排油煙管內風速超過每秒五公尺者應在警戒長度外側設置放出藥劑之啟動裝置及連動閉鎖閘門,防護範圍內之噴頭應一齊放射,儲存鋼瓶及加壓氣體鋼瓶設於攝氏四十度以下之位置,而警戒長度指煙罩與排油煙管接合處往內五公尺。《消防安全設備測試報告書測試方法及判定要領》簡易自動滅火設備之外觀試驗另要求控制裝置設在環境溫度 49℃ 以下之場所,本體應標示「廚房簡易自動滅火裝置」字樣。至於同基準惰性氣體滅火設備之性能檢查,除藥劑量差值在充填值 10％以下外,共同事項還載明二氧化碳滅火設備之充填比應在 1.5 以上,並提醒容器重量約 150 公斤、搬動時應注意傾倒——不同設備的容許差與注意事項要分章記,不要互相套用。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-water-chemical-022","有關水道連結型自動撒水設備進行綜合檢查時，其放水壓力應為多少？",22,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-water-chemical-024","十樓以下建築物之樓層供百貨商場使用，如達到設置自動撒水設備條件，使用密閉式一般反應型撒水頭時，其水源容量應符合幾個撒水頭放水 20 分鐘的撒水量？",24,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-water-chemical-021","下列有關乾粉滅火設備設置之規定，何者正確？",21,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-water-chemical-025","泡沫試料淨重為 200 g，還原數值如下，則 25%還原時間為何？時間（分） 0 0.5 1 1.5 2 2.5 3 還原量（ml） 0 10 20 30 40 50 60",25,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-water-chemical-020","電子工業廠房潔淨室設置消防安全設備，下列敘述何者正確？",20,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-water-chemical-026","壓力開關高程 0 m，屋頂水箱高程 33 m，最高處撒水頭高程 30 m，加壓送水裝置利用啟動用壓力開關連動啟動。當壓力開關小於何值時，加壓送水裝置即應啟動？",26,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-water-chemical-023",110,"下列場所何者可選擇第二種室內消防栓選擇設置之？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-water-chemical-023",109,"下列有關室內消防栓箱之敘述，何者正確？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-water-chemical-023",108,"依各類場所消防安全設備設置標準之規定，有關應設置室外消防栓設備之場所，下列敘述何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-water-chemical-023",107,"有關室內消防栓綜合檢查放水量及放水壓力之敘述，下列何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-water-chemical-023",106,"泡沫滅火設備進行綜合檢查時，有關蛋白質泡沫滅火藥劑之發泡倍率至少應為何？",1785123166320]