[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-water-chemical-027":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":52,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-水與化學系統消防安全設備概要-027","fire-111-1-water-chemical-027",111,1,27,"自動撒水採用密閉乾式或預動式自動撒水設備，撒水頭動作後，流水檢知裝置應在幾分鐘內，使撒水頭放水？",{"A":16,"B":17,"C":18,"D":19},"4","3","2","1","D",null,[],false,"本題考點：密閉乾式與預動式自動撒水設備,自撒水頭動作到實際放水的時間上限。\n【正解理由】依《各類場所消防安全設備設置標準》第 55 條第三款,密閉乾式或預動式自動撒水設備「撒水頭動作後,流水檢知裝置應在一分鐘內,使撒水頭放水」;《消防安全設備測試報告書測試方法及判定要領》自動撒水設備綜合試驗對使用密閉式撒水頭者,也把「如為乾式或預動式者,應在一分鐘以內放水」列為判定要領,兩者一致,故選 D。\n【逐項排除】\n(A) 4 分鐘不是第 55 條所定值;該條另一個與時間有關的數字是第一款空氣壓縮機應能在三十分鐘內加壓達流水檢知裝置二次側配管之設定壓力值,與放水時間無關。\n(B) 3 分鐘同樣不是條文所定之放水時限。\n(C) 2 分鐘亦非條文數值,條文所定放水時限為一分鐘。\n(D) 1 分鐘與第 55 條第三款及綜合試驗判定要領相符,為正解。\n【記憶點】乾式與預動式:空氣壓縮機三十分鐘充壓、撒水頭動作後一分鐘內放水。","為什麼只有乾式與預動式要另定放水時限?看第 43 條的型式定義就懂:密閉濕式平時管內貯滿高壓水,撒水頭動作時即撒水;密閉乾式平時管內貯滿高壓空氣,撒水頭動作時先排空氣、繼而撒水;開放式平時管內無水,啟動一齊開放閥使水流入管系撒水;預動式平時管內貯滿低壓空氣,以感知裝置啟動流水檢知裝置,且撒水頭動作時即撒水。乾式與預動式的二次側是空氣,撒水頭動作後必須先把空氣排掉水才會到,所以第 55 條才要求流水檢知裝置在一分鐘內使撒水頭放水,避免初期滅火時機被排氣過程耗掉。\n同條其他三款也常一起考:第一款空氣壓縮機為專用,並能在三十分鐘內加壓達流水檢知裝置二次側配管之設定壓力值;第二款二次側之減壓警報設於平時有人處;第四款撒水頭使用向上型,但配管能採取有效措施者不在此限。配管面依第 44 條,密閉乾式或預動式之流水檢知裝置二次側配管應施予鍍鋅等防腐蝕處理,並為有效排水,支管每十公尺傾斜四公分、主管每十公尺傾斜二公分,於明顯易見處設排水閥並標明排水閥字樣。《消防安全設備及必要檢修項目檢修基準》自動撒水設備之性能檢查則要求關閉乾式或預動式一次側之制水閥後,打開二次側配管之排水閥確認是否能適當排水,判定為配管之二次側應無積水。另可留意第 211 條:公共危險物品等場所在使用密閉乾式或預動式流水檢知裝置時,水源容量之撒水頭數量應追加十個;該條屬第四編,僅適用於公共危險物品或可燃性高壓氣體場所,不得套用於一般場所。",true,[28,32,36,40,44,48],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-water-chemical-026","壓力開關高程 0 m，屋頂水箱高程 33 m，最高處撒水頭高程 30 m，加壓送水裝置利用啟動用壓力開關連動啟動。當壓力開關小於何值時，加壓送水裝置即應啟動？",26,{"webId":33,"stem":34,"number":35,"year":11,"session":12},"fire-111-1-water-chemical-028","依各類場所消防安全設備設置標準之規定，下列何者應設自動撒水設備？",28,{"webId":37,"stem":38,"number":39,"year":11,"session":12},"fire-111-1-water-chemical-025","泡沫試料淨重為 200 g，還原數值如下，則 25%還原時間為何？時間（分） 0 0.5 1 1.5 2 2.5 3 還原量（ml） 0 10 20 30 40 50 60",25,{"webId":41,"stem":42,"number":43,"year":11,"session":12},"fire-111-1-water-chemical-029","變電站場所設置水霧滅火設備，放射區域 6 個分區，其消防幫浦出水量需達每分鐘 X 公升以上；且每顆水霧噴頭放水壓力均能達每平方公分 Y 公斤以上，請問前述 X、Y 為何？",29,{"webId":45,"stem":46,"number":47,"year":11,"session":12},"fire-111-1-water-chemical-024","十樓以下建築物之樓層供百貨商場使用，如達到設置自動撒水設備條件，使用密閉式一般反應型撒水頭時，其水源容量應符合幾個撒水頭放水 20 分鐘的撒水量？",24,{"webId":49,"stem":50,"number":51,"year":11,"session":12},"fire-111-1-water-chemical-030","有關消防安全設備檢修完成標示附加位置，下列敘述何者錯誤？",30,[53,57,61,65,69],{"webId":54,"year":55,"stem":56,"number":13},"fire-110-1-water-chemical-027",110,"二氧化碳滅火設備之全區放射或局部放射方式防護區域，對放射之滅火藥劑之排放規定，下列何者錯誤？",{"webId":58,"year":59,"stem":60,"number":13},"fire-109-1-water-chemical-027",109,"中央消防主管機關認定儲存大量可燃物之場所天花板高度超過 6 公尺，或其他場所天花板高度超過 10 公尺者，應採用何種撒水頭？",{"webId":62,"year":63,"stem":64,"number":13},"fire-108-1-water-chemical-027",108,"依各類場所消防安全設備設置標準之規定，室外消防栓於其 I 公尺範圍內附設水帶箱，在 J 公尺以內，保持空曠，不得堆放物品或種植花木。下列 I，J 何者正確？",{"webId":66,"year":67,"stem":68,"number":13},"fire-107-1-water-chemical-027",107,"有關二氧化碳滅火設備放射時間之敘述，下列何者正確？",{"webId":70,"year":71,"stem":72,"number":13},"fire-106-1-water-chemical-027",106,"依各類場所消防安全設備設置標準，連結送水管之出水口設置，下列敘述何者錯誤？",1785123166368]