[{"data":1,"prerenderedAt":73},["ShallowReactive",2],{"q-fire-111-1-water-chemical-040":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":53,"hasEssay":26},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-111-1-水與化學系統消防安全設備概要-040","fire-111-1-water-chemical-040",111,1,40,"二氧化碳滅火設備採全區放射方式，採用高壓系統在進行綜合檢查時，以空氣或氮氣進行放射試驗，所需空氣量或氮氣量，應就放射區域應設滅火藥劑量之 X%核算，每公斤核算空氣量或氮氣量 Y（公升），請問前述 X、Y 為何？",{"A":16,"B":17,"C":18,"D":19},"X=5；Y=45","X=10；Y=55","X=15；Y=60","X=20；Y=65","B",null,[],false,"本題考點：《消防安全設備及必要檢修項目檢修基準》惰性氣體滅火設備之綜合檢查，全區放射方式高壓式者放射試驗所需空氣量或氮氣量之核算。\n【正解理由】該章綜合檢查就全區放射方式高壓式者規定，以空氣或氮氣進行放射試驗，所需空氣量或氮氣量應就放射區域應設滅火藥劑量之 10％核算，每公斤以所附表格所列公升數之比例核算，每次試驗最多放出 5 支；該表所列二氧化碳每公斤核算空氣量或氮氣量為 55 公升。X 為 10、Y 為 55，故選 B。\n【逐項排除】\n(A) 比例 5％與每公斤 45 公升，於該章綜合檢查本文及所附表格均無所據。\n(B) 10％與二氧化碳每公斤 55 公升，與該章綜合檢查所定之比例及表列值相符，為本題答案。\n(C) 15％非該章所定之核算比例，60 公升亦非表列之每公斤核算量。\n(D) 20％非該章所定之核算比例，65 公升亦非表列之每公斤核算量。\n【記憶點】綜合檢查放射試驗一律取應設滅火藥劑量之 10％；每公斤核算量二氧化碳 55 公升，氮氣、IG-55、IG-541 均為 100 公升。","綜合檢查的放射試驗不可能真的把整區藥劑放光，因此檢修基準採「以空氣或氮氣替代、按比例取樣」的設計。《消防安全設備及必要檢修項目檢修基準》惰性氣體滅火設備之綜合檢查就全區放射方式高壓式者定：應就放射區域應設滅火藥劑量之 10％核算所需空氣量或氮氣量，每公斤以表列公升數之比例核算，每次試驗最多放出 5 支；表列值為二氧化碳 55 公升、氮氣 100 公升、IG-55 100 公升、IG-541 100 公升。低壓式者則另定，放射試驗所需之藥劑量為該放射區域所設滅火藥劑量之 10％以上，或使用 40 公升氮氣 5 瓶以上作為替代藥劑放射。\n相同的 10％比例在其他氣體系統章節重複出現，差別只在每公斤核算量，可並列記憶：海龍滅火設備之綜合檢查同樣就應設滅火藥劑量之 10％核算，其表列值為海龍 2402 為 9 公升、海龍 1211 為 15 公升、海龍 1301 為 16 公升；鹵化烴滅火設備之表列值為 HFC-23 為 34 公升、HFC-227ea 為 14 公升，並同樣定每次試驗最多放出 5 支。乾粉滅火設備則不換算公升數，而是直接以氣體量計：加壓式放射試驗所需試驗用氣體量為該放射區域應設加壓用氣體之 10％以上（小數點以下有尾數時進一），蓄壓式為該放射區域應設蓄壓用氣體量之 10％以上。\n抽樣方式也是常考點：全區放射方式應依設置之系統數量進行抽樣檢查，抽測之系統放射區域在二區以上時，應至少擇一放射區域實施放射試驗，並應於滅火藥劑儲存容器標示放射日期；抽樣分配表以系統設置套數對應第一年至第十年，系統設置數量超過二十一套者依其比例類推分配。判定方法各章共通，可整套背下：警報裝置應確實鳴響、遲延裝置應確實動作、開口部等之自動關閉裝置應能正常動作且換氣裝置須確實停止、指定防護區劃之啟動裝置及選擇閥能確實動作並可放射試驗用氣體、配管內之試驗用氣體應無洩漏情形、放射表示燈應確實亮燈。",true,[28,32,37,41,45,49],{"webId":29,"stem":30,"number":31,"year":11,"session":12},"fire-111-1-water-chemical-039","可燃性高壓氣體儲存場所任一點至滅火器之步行距離在 X 公尺以下，並不得妨礙出入作業；每具滅火器對普通火災具有 Y 個以上之滅火效能值，請問前述 X、Y 為何？",39,{"webId":33,"stem":34,"number":35,"year":36,"session":12},"fire-112-1-water-chemical-004","依水道連結型自動撒水設備設置基準之規定，採民生水箱共用式，其配管、配件及閥類之規定，下列敘述何者錯誤？",4,112,{"webId":38,"stem":39,"number":40,"year":11,"session":12},"fire-111-1-water-chemical-038","一間變壓機房採全區放射二氧化碳滅火設備，其防護區域體積 1250 立方公尺，無其它開口部，此防護區域需要多少二氧化碳藥劑量？",38,{"webId":42,"stem":43,"number":35,"year":44,"session":12},"fire-114-1-water-chemical-004","依各類場所消防安全設備設置標準規定，鹵化烴滅火設備，蓄壓式儲存容器儲存 HFC-227ea、 FK-5-1-12 之儲存壓力，應以氮氣加壓至 X MPa 以上。加壓式儲存容器，應設置可調整壓力至 Y MPa 之壓力調整裝置。則 X+Y 為多少？",114,{"webId":46,"stem":47,"number":48,"year":11,"session":12},"fire-111-1-water-chemical-037","依規定 112 年度滅火器檢查合格時，應採用那種顏色檢修環？",37,{"webId":50,"stem":51,"number":12,"year":52,"session":12},"fire-106-1-water-chemical-001","依 NFPA 2001 之規定，潔淨式氣體滅火系統於一般場所之藥劑放射時間（達設計濃度 95%之時間），下列何者錯誤？",106,[54,58,62,66,70],{"webId":55,"year":56,"stem":57,"number":13},"fire-110-1-water-chemical-040",110,"依消防安全設備及必要檢修項目檢修基準，冷卻撒水設備之供第四類公共危險物品之顯著滅火困難場所之加壓送水裝置，啟動後 X 分鐘內應能有效撒水，且加壓送水裝置距撒水區域在 Y 公尺以下，但設有保壓措施者不在此限。X、Y 分別為何？",{"webId":59,"year":60,"stem":61,"number":13},"fire-109-1-water-chemical-040",109,"儲槽規定設置補助泡沫消防栓時，下列敘述何者錯誤？",{"webId":63,"year":64,"stem":65,"number":13},"fire-108-1-water-chemical-040",108,"電動機之使用應符合之相關規定，下列何者錯誤？",{"webId":67,"year":68,"stem":69,"number":13},"fire-107-1-water-chemical-040",107,"進行幫浦性能試驗時，幫浦之出水量在額定出水量之 1.5 倍時，其全揚程應為額定出水量在性能曲線上全揚程百分之多少以上？",{"webId":71,"year":52,"stem":72,"number":13},"fire-106-1-water-chemical-040","有一長 15 公尺、寬 12 公尺及高 3 公尺之密閉空間裝置二氧化碳滅火設備，假設空氣中氧氣之體積百分率濃度為 21%，在溫度壓力固定下，欲使氧氣濃度降至 15%以下，需注入多少立方公尺之二氧化碳？",1785123166500]