[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-112-1-alarm-evacuation-031":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":25,"sameNumber":50,"hasEssay":68},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":24,"freq":12,"indexable":23},"fire-112-1-警報與避難系統消防安全設備概要-031","fire-112-1-alarm-evacuation-031",112,1,31,"依消防安全設備及必要檢修項目檢修基準，執行緊急廣播設備性能檢查時，對啟動裝置狀態於檢查後判定方法，下列敘述何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"手動按鈕開關在操作部應發出音響警報及火災音響信號","於受信火災信號後與火警自動警報設備之連動時，自動地啟動廣播設備，其火災音響信號或音響裝置應鳴動","在受信火災信號後與火警自動警報設備之連動時，起火層表示燈至火災信號復舊前，應保持亮燈","火警自動警報設備之手動報警機應能任意選擇通話，且此時被遮斷之緊急電話就不應聽到講話音","D",null,[],false,"",[26,31,35,39,43,47],{"webId":27,"stem":28,"number":29,"year":30,"session":12},"fire-107-1-alarm-evacuation-027","依各類場所消防安全設備設置標準規定，緊急供電系統之配線除依屋內線路裝置規則外，緊急用電源回路及操作回路，應使用多少伏特耐熱絕緣電線，或同等耐熱效果以上之電線？",27,107,{"webId":32,"stem":33,"number":34,"year":30,"session":12},"fire-107-1-alarm-evacuation-029","依各類場所消防安全設備設置標準規定，有關標示設備之敘述，何者正確？",29,{"webId":36,"stem":37,"number":38,"year":30,"session":12},"fire-107-1-alarm-evacuation-026","依各類場所消防安全設備設置標準規定，緊急供電系統之配線除依屋內線路裝置規則外，有關電源回路之配線耐燃保護，若電線裝於金屬導線管槽內，並埋設於防火構造物之混凝土內，混凝土保護厚度應為多少毫米以上？",26,{"webId":40,"stem":41,"number":42,"year":30,"session":12},"fire-107-1-alarm-evacuation-030","偵煙式探測器除光電式分離型外，下列裝置規定何者錯誤？",30,{"webId":44,"stem":45,"number":46,"year":30,"session":12},"fire-107-1-alarm-evacuation-025","有一飯店，其三樓之樓地板面積為 1200 平方公尺，依各類場所消防安全設備設置標準規定，於設置出口標示燈時，除應使用 A 級或 B 級外，出口標示燈標示面光度應在多少燭光（cd）以上？",25,{"webId":48,"stem":49,"number":13,"year":30,"session":12},"fire-107-1-alarm-evacuation-031","依各類場所消防安全設備設置標準規定，公共危險物品製造場所及一般處理場所總樓地板面積在多少平方公尺以上者，應設置火警自動警報設備？",[51,55,59,63,64],{"webId":52,"year":53,"stem":54,"number":13},"fire-110-1-alarm-evacuation-031",110,"一一九火災通報裝置，下列規定何者正確？",{"webId":56,"year":57,"stem":58,"number":13},"fire-109-1-alarm-evacuation-031",109,"有關緊急照明設備性能檢查之判定方法與注意事項，下列何者與各類場所消防安全設備檢修及申報作業基準之規定不同？",{"webId":60,"year":61,"stem":62,"number":13},"fire-108-1-alarm-evacuation-031",108,"依各類場所消防安全設備設置標準對於出口標示燈設置之相關規定，下列何者正確？",{"webId":48,"year":30,"stem":49,"number":13},{"webId":65,"year":66,"stem":67,"number":13},"fire-106-1-alarm-evacuation-031",106,"在某飯店檢查瓦斯漏氣火警自動警報設備，進行檢知器之性能檢查時，發現同一個檢知回路上裝設有 18 個瓦斯漏氣檢知器，至少應選取多少個進行試驗？",true,1785123170125]