[{"data":1,"prerenderedAt":70},["ShallowReactive",2],{"q-fire-112-1-fire-law-004":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":53,"hasEssay":26},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-112-1-消防法規概要-004","fire-112-1-fire-law-004",112,1,4,"水霧滅火設備之放射區域在二區域以上時，其水源容量應保持 X 立方公尺以上；消防幫浦每分鐘出水量應為 Y 公升以上，下列敘述何者正確？",{"A":16,"B":17,"C":18,"D":19},"X=20；Y=2500","X=40；Y=2000","X=20；Y=1500","X=40；Y=1200","B",null,[],false,"本題考點：《各類場所消防安全設備設置標準》對水霧滅火設備水源容量與加壓送水裝置出水量的規定，且放射區域在二區域以上時兩項數值均須加倍。\n【正解理由】依《各類場所消防安全設備設置標準》第64條，水霧滅火設備之水源容量應保持20立方公尺以上，但放射區域在二區域以上者，應保持40立方公尺以上；同標準第65條，加壓送水裝置之出水量每分鐘應在1200公升以上，放射區域在二區域以上者，每分鐘應在2000公升以上。題幹條件既為二區域以上，X須取40、Y須取2000，故選B。\n【逐項排除】\n(A) X=20是單一放射區域的水源容量，直接用在二區域以上會短少一半；Y=2500亦非條文所列之出水量級距，兩個數值都不成立。\n(B) 40立方公尺搭配每分鐘2000公升，正是條文對二區域以上場所所定的加倍值，水源與幫浦能力同步提升，敘述正確。\n(C) X=20同樣誤用單一放射區域的水量；Y=1500介於1200與2000之間，條文並無此門檻，屬自行編造的數值。\n(D) X=40的水源容量正確，但Y=1200是單一放射區域的出水量下限，用於二區域以上將低於法定出水量，故整組敘述仍錯。\n【記憶點】水霧放射區域一變二，「水源20變40、出水1200變2000」，水量與出水量一起翻倍記。","水霧滅火設備在《各類場所消防安全設備設置標準》第61條至第66條自成一節，設計思維與自動撒水設備不同：撒水是以較大水滴直接冷卻並潤濕可燃物，水霧則把水打散成微細水粒，靠冷卻、窒息（水汽化後體積膨脹排擠氧氣）、乳化與稀釋四種作用滅火，因此常用於停車空間、電氣設備室、危險物品場所這類不宜大量注水的空間。理解這個設計目的，就能理解為何條文要用「放射區域」而非樓地板面積來決定水量：一個放射區域代表一次同時放水的防護範圍，區域數愈多，同時放水量愈大，水源與幫浦自然要跟著加碼。\n數值上有一組必須成套記住：每一水霧噴頭之放水量在每分鐘50公升以上（第61條），放水量須使防護區域每平方公尺每分鐘達10公升以上，每一放射區域以50平方公尺以上為原則（第63條），水源容量20立方公尺、二區域以上40立方公尺（第64條），加壓送水裝置出水量每分鐘1200公升、二區域以上2000公升（第65條）。單位換算是常見陷阱：1立方公尺等於1000公升，40立方公尺即40000公升，除以每分鐘2000公升，恰可連續放水20分鐘，這正是條文水量與出水量相互對應的由來，也是驗算選項合理性的快速方法——選項中1200與40立方公尺搭配會得出33分鐘，2500與40立方公尺得16分鐘，都不符合設計上二十分鐘的一致性。\n易混淆之處在於同屬水系統的三種設備水源要求：室內消防栓為第一種每支瞄子放水量每分鐘130公升、水源以2支計算；自動撒水設備依放水壓力與撒水頭數計算水源；水霧則走「放射區域」制。另外水霧設備尚須依第66條設置排水設備，因為水霧用於停車空間時必須攔阻含油廢水，這也是常見的延伸考點。以放射區域為核心，把水源、出水量、排水三者一起背，同一條文改考任何一項都能對應。",true,[28,33,37,41,45,49],{"webId":29,"stem":30,"number":31,"year":32,"session":12},"fire-111-1-fire-law-040","依建築技術規則建築設計施工編規定，有關分戶牆及分間牆構造，下列敘述何者正確？",40,111,{"webId":34,"stem":35,"number":13,"year":36,"session":12},"fire-114-1-fire-law-004","達管制量之公共危險物品及可燃性高壓氣體製造場所，其位置、構造、設備未符合公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法規定，處其管理權人之罰鍰為何？",114,{"webId":38,"stem":39,"number":40,"year":32,"session":12},"fire-111-1-fire-law-039","避難器具裝置在固定部上之固定器具材料如為鋼材，其鋼索之容許拉伸應力為剪斷荷重的多少比例？",39,{"webId":42,"stem":43,"number":12,"year":44,"session":12},"fire-115-1-fire-law-001","依消防法規定，下列何者應委託中央主管機關許可之消防安全設備檢修專業機構辦理檢修申報？ ①複合用途建築物 ②地下建築物 ③高層建築物 ④大型集合住宅",115,{"webId":46,"stem":47,"number":48,"year":32,"session":12},"fire-111-1-fire-law-038","有關加壓送水裝置之電動機，其種類、構造及機能等之敘述，何者正確？",38,{"webId":50,"stem":51,"number":12,"year":52,"session":12},"fire-106-1-fire-law-001","依規定應設置消防安全設備之場所，其管理權人應委託消防設備師或消防設備士定期檢修消防安全設備，其檢修方式中之綜合檢查係指下列何者？",106,[54,55,58,62,66],{"webId":34,"year":36,"stem":35,"number":13},{"webId":56,"year":32,"stem":57,"number":13},"fire-111-1-fire-law-004","國內建築型態日益多元，使災害預防及搶救複雜程度增加，下列內容何者非防災中心服勤人員訓練要點之規定？",{"webId":59,"year":60,"stem":61,"number":13},"fire-110-1-fire-law-004",110,"某 KTV 之管理權人未依規定維護該場所之消防安全設備，導致火災發生時，消防安全設備無法發揮正常功能，而造成二名消費者死亡，依消防法之規定，對管理權人之處分，下列敘述何者正確？",{"webId":63,"year":64,"stem":65,"number":13},"fire-109-1-fire-law-004",109,"依消防法施行細則之規定，針對消防安全設備施工中須經試驗或勘驗事項之查核，並製作紀錄是屬於下列那個項目之內容？",{"webId":67,"year":68,"stem":69,"number":13},"fire-108-1-fire-law-004",108,"檢修機構聘用、資遣、解聘消防設備師或消防設備士，應於事實發生之日起幾日內，檢附文件報請內政部備查？",1785123156811]