[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-112-1-fire-law-030":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":25,"sameNumber":50,"hasEssay":71},"消防法規概要","fire-law","消防法規 · Fire Code","消防法規",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":24,"freq":12,"indexable":23},"fire-112-1-消防法規概要-030","fire-112-1-fire-law-030",112,1,30,"依消防安全設備及必要檢修項目檢修基準之規定，有關惰性氣體滅火設備之綜合檢查，下列敘述何者正確？",{"A":16,"B":17,"C":18,"D":19},"全區放射方式之系統設置數量為 15 套者，第 5 年應抽樣 2 套系統進行檢查。抽測之系統放射區域在 2 區以上時，應至少擇一放射區域實施放射試驗","全區放射方式之高壓式系統且滅火藥劑為二氧化碳者，以空氣或氮氣進行放射試驗，所需空氣或氮氣量以放射區域應設滅火藥劑量之 10%且每公斤 50 公升之比例核算，每次試驗最多放出 5 支","全區放射方式之高壓式系統且滅火藥劑為 IG-541 者，以空氣或氮氣進行放射試驗，所需空氣或氮氣量以放射區域應設滅火藥劑量之 10%且每公斤 100 公升之比例核算，每次試驗最多放出 5 支","全區放射方式之低壓式系統且滅火藥劑為 IG-55 者，進行放射試驗所需之藥劑量，為該放射區域所設滅火藥劑量之 10%以上，或使用 50 公升氮氣 5 瓶以上作為替代藥劑放射","C",null,[],false,"",[26,31,35,39,43,47],{"webId":27,"stem":28,"number":29,"year":30,"session":12},"fire-106-1-fire-law-026","下列有關防火水幕設備之水源容量規定之敘述，何者錯誤？",26,106,{"webId":32,"stem":33,"number":34,"year":30,"session":12},"fire-106-1-fire-law-028","依可燃性高壓氣體儲存場所防護牆設置基準規定，鋼筋混凝土製防護牆，其厚度應在多少 mm 以上？",28,{"webId":36,"stem":37,"number":38,"year":30,"session":12},"fire-106-1-fire-law-025","依公共危險物品及可燃性高壓氣體設置標準暨安全管理辦法規定，下列有關六類物品製造場所之敘述，何者正確？",25,{"webId":40,"stem":41,"number":42,"year":30,"session":12},"fire-106-1-fire-law-029","下列有關簡易自動滅火設備規定之敘述，何者錯誤？",29,{"webId":44,"stem":45,"number":46,"year":30,"session":12},"fire-106-1-fire-law-024","下列有關消防安全設備檢修專業機構管理辦法規定之敘述，何者錯誤？",24,{"webId":48,"stem":49,"number":13,"year":30,"session":12},"fire-106-1-fire-law-030","下列有關百貨商場收容人員之計算規定之敘述，何者錯誤？",[51,55,59,63,67],{"webId":52,"year":53,"stem":54,"number":13},"fire-111-1-fire-law-030",111,"依各類場所消防安全設備設置標準規定，某樓層高度超過 10 公尺且樓地板面積在 700 平方公尺以上之高架儲存倉庫，其撒水頭設置應符合之規定，下列敘述何者正確？",{"webId":56,"year":57,"stem":58,"number":13},"fire-110-1-fire-law-030",110,"可燃性高壓氣體儲存場所防爆牆分為鋼筋混凝土製、混凝土空心磚製及鋼板製等三種，並應設置於堅固基礎上，強度應能承受可能預料之氣體爆炸衝擊，有關混凝土空心磚製防爆牆之規定，下列敘述何者正確？",{"webId":60,"year":61,"stem":62,"number":13},"fire-109-1-fire-law-030",109,"依各類場所消防安全設備檢修及申報作業基準，有關避難器具外觀檢查之規定，緩降機下降空間之判定，在無其他突出物干擾的情境下，以器具中心半徑多少公分的圓柱形範圍內，為緩降機的下降空間？",{"webId":64,"year":65,"stem":66,"number":13},"fire-108-1-fire-law-030",108,"依各類場所消防安全設備設置標準規定，下列何種處所得免設排煙設備？",{"webId":68,"year":69,"stem":70,"number":13},"fire-107-1-fire-law-030",107,"依各類場所消防安全設備設置標準之規定，下列何者應設置連結送水管？",true,1785123157126]