[{"data":1,"prerenderedAt":72},["ShallowReactive",2],{"q-fire-112-1-water-chemical-039":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":25,"sameNumber":50,"hasEssay":71},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":24,"freq":12,"indexable":23},"fire-112-1-水與化學系統消防安全設備概要-039","fire-112-1-water-chemical-039",112,1,39,"依各類場所消防安全設備設置標準規定，消防專用蓄水池之採水設置，下列敘述何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"有效水量計算，蓄水池深度得超過在基地地面下 4.5 公尺範圍內之水量","水量 40 立方公尺以上 120 立方公尺未滿，加壓送水裝置出水量 2,200(l\u002Fmin)及採水口數 3 個","加壓送水裝置應於採水口附近設啟動裝置及紅色啟動表示燈。但設有能由防災中心遙控啟動，且採水口與防災中心間設有通話連絡裝置者，不在此限","採水口接裝 63 毫米陽式快接頭，距離基地地面之高度在 1 公尺以下 0.5 公尺以上","B",null,[],false,"",[26,31,35,39,42,46],{"webId":27,"stem":28,"number":29,"year":30,"session":12},"fire-106-1-water-chemical-036","低壓式二氧化碳噴頭之放射壓力為每平方公分多少公斤以上？",36,106,{"webId":32,"stem":33,"number":34,"year":30,"session":12},"fire-106-1-water-chemical-038","乾粉全區放射所核算之滅火藥劑量須於幾秒內放射完畢？",38,{"webId":36,"stem":37,"number":38,"year":30,"session":12},"fire-106-1-water-chemical-035","乾式比濕式系統的撒水頭數量應追加百分之多少？",35,{"webId":40,"stem":41,"number":13,"year":30,"session":12},"fire-106-1-water-chemical-039","泡沫滅火設備使用低發泡水成膜泡沫液，其泡沫 25%還原時間應在多少分鐘以上？",{"webId":43,"stem":44,"number":45,"year":30,"session":12},"fire-106-1-water-chemical-034","第一種乾粉滅火藥劑，全區放射方式所需滅火藥劑量為多少 kg\u002Fm ？",34,{"webId":47,"stem":48,"number":49,"year":30,"session":12},"fire-106-1-water-chemical-040","有一長 15 公尺、寬 12 公尺及高 3 公尺之密閉空間裝置二氧化碳滅火設備，假設空氣中氧氣之體積百分率濃度為 21%，在溫度壓力固定下，欲使氧氣濃度降至 15%以下，需注入多少立方公尺之二氧化碳？",40,[51,55,59,63,67],{"webId":52,"year":53,"stem":54,"number":13},"fire-111-1-water-chemical-039",111,"可燃性高壓氣體儲存場所任一點至滅火器之步行距離在 X 公尺以下，並不得妨礙出入作業；每具滅火器對普通火災具有 Y 個以上之滅火效能值，請問前述 X、Y 為何？",{"webId":56,"year":57,"stem":58,"number":13},"fire-110-1-water-chemical-039",110,"依消防安全設備及必要檢修項目檢修基準，冷卻撒水設備之遠隔啟動裝置，限用於儲存閃火點多少℃以下公共危險物品之室外儲槽？",{"webId":60,"year":61,"stem":62,"number":13},"fire-109-1-water-chemical-039",109,"公共危險品等場所中，所設置之室外消防栓設備，其緊急電源之供電容量應供其有效動作多久以上？",{"webId":64,"year":65,"stem":66,"number":13},"fire-108-1-water-chemical-039",108,"依各類場所消防安全設備設置標準之規定，公共危險物品室外儲槽場所之冷卻撒水設備如以幫浦方式進行加壓時，實際測得之放射量除以該冷卻撒水噴頭（噴孔）所防護儲槽側壁面積應在多少以上？",{"webId":68,"year":69,"stem":70,"number":13},"fire-107-1-water-chemical-039",107,"為執行檢修申報，針對水霧滅火系統綜合檢查，對於判定方法之敘述，下列何者正確？",true,1785123166062]