[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-113-1-water-chemical-011":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":25,"sameNumber":50,"hasEssay":68},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":24,"freq":12,"indexable":23},"fire-113-1-水與化學系統消防安全設備概要-011","fire-113-1-water-chemical-011",113,1,11,"室內消防栓進行檢修之綜合檢查，依據消防安全設備及必要檢修項目檢修基準規定，下列敘述何者錯誤？",{"A":16,"B":17,"C":18,"D":19},"於裝置消防栓最多之最高樓層做放水試驗，以該樓層全部消防栓放水為準，但消防栓超過二支時，以二支同時放水","測量瞄子直線放水之壓力時，將壓力表之進水口放置於瞄子前端瞄子口徑的三分之一距離處，讀取壓力表的指示值","公共危險物品等場所達顯著滅火困難者設置消防栓之數量超過五支時，以五支同時放水","公共危險物品等場所達顯著滅火困難者設置之第一種滅火設備之消防栓，其放水壓力應在每平方公分 3.5 公斤以上每平方公分 7 公斤以下","B",null,[],false,"",[26,31,35,39,42,46],{"webId":27,"stem":28,"number":29,"year":30,"session":12},"fire-107-1-water-chemical-008","水滅火系統中，以立管連接屋頂水箱使配管平時充滿水，屋頂水箱之容量要求，下列何者錯誤？",8,107,{"webId":32,"stem":33,"number":34,"year":30,"session":12},"fire-107-1-water-chemical-010","第一種室內消防栓採用消防幫浦做為加壓送水裝置時，假設水帶摩擦損失水頭為 3 m，配管磨擦損失水頭為 7 m，落差為 30 m，則依規定，幫浦的全揚程應為多少公尺？",10,{"webId":36,"stem":37,"number":38,"year":30,"session":12},"fire-107-1-water-chemical-007","自動撒水設備應裝置適當之流水檢知裝置，有關流水檢知裝置之設置規定，下列何者正確？",7,{"webId":40,"stem":41,"number":13,"year":30,"session":12},"fire-107-1-water-chemical-011","加壓式乾粉滅火設備，於啟動裝置動作後，為使儲存容器壓力達設定壓力始開啟放出閥，應設置何種裝置？",{"webId":43,"stem":44,"number":45,"year":30,"session":12},"fire-107-1-water-chemical-006","泡沫滅火系統中，採高發泡全區放射時，冠泡體積係指防護區域自樓地板面至高出防護對象最高點多少公尺所圍體積？",6,{"webId":47,"stem":48,"number":49,"year":30,"session":12},"fire-107-1-water-chemical-012","設置乾粉滅火設備時，全區及局部放射之緊急電源應為自用發電設備或蓄電池設備，其容量應能使設備有效動作多久以上？",12,[51,55,59,63,67],{"webId":52,"year":53,"stem":54,"number":13},"fire-111-1-water-chemical-011",111,"依各類場所消防安全設備設置標準規定，消防專用蓄水池應設置於消防車能接近至多少公尺範圍內，易於抽取處？",{"webId":56,"year":57,"stem":58,"number":13},"fire-110-1-water-chemical-011",110,"室內消防栓設備之加壓送水裝置，若採用壓力水箱方式，則其水箱內空氣不得小於水箱容積的幾分之幾？",{"webId":60,"year":61,"stem":62,"number":13},"fire-109-1-water-chemical-011",109,"乾粉滅火設備之緊急電源應為發電機設備或蓄電池設備，其容量應能使該設備有效動作多少時間以上？",{"webId":64,"year":65,"stem":66,"number":13},"fire-108-1-water-chemical-011",108,"二氧化碳滅火設備使用氣體啟動者，啟動用氣體容器之內容積應有 1 公升以上，其所儲存之二氧化碳重量在 0.6 公斤以上，且其充填比應在多少以上？",{"webId":40,"year":30,"stem":41,"number":13},true,1785123165313]