[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-113-1-water-chemical-036":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":25,"sameNumber":50,"hasEssay":68},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":24,"freq":12,"indexable":23},"fire-113-1-水與化學系統消防安全設備概要-036","fire-113-1-water-chemical-036",113,1,36,"有關室外消防栓測試方法及判定要領，下列何者與消防安全設備測試報告書規定不同？",{"A":16,"B":17,"C":18,"D":19},"消防栓開關閥應設置在距離樓地板面高度 1.5 公尺以下的位置或在樓地板面以下深 0.6 公尺以內的位置","消防栓地下式之水帶接續口應設置在樓地板面以下深 0.3 公尺以內的位置","箱面應有明顯不易脫落之「水帶箱」字樣，每字不得小於 20 平方公分","室外消防栓與建築物一樓外牆各部分之水平距離，不得超過 30 公尺","D",null,[],false,"",[26,31,35,39,42,46],{"webId":27,"stem":28,"number":29,"year":30,"session":12},"fire-107-1-water-chemical-033","自動撒水設備竣工時進行加壓試驗，下列何者錯誤？",33,107,{"webId":32,"stem":33,"number":34,"year":30,"session":12},"fire-107-1-water-chemical-035","採用移動式放射方式之乾粉滅火設備，藥劑種類為第一種乾粉時，每一具噴射瞄子所需藥劑放射量為：",35,{"webId":36,"stem":37,"number":38,"year":30,"session":12},"fire-107-1-water-chemical-032","泡沫滅火設備之場所，於進行性能檢查時，製造年份超過幾年或無法辨識製造年份之水帶，應進行水壓試驗？",32,{"webId":40,"stem":41,"number":13,"year":30,"session":12},"fire-107-1-water-chemical-036","有關自動撒水設備末端查驗閥之敘述，下列何者正確？",{"webId":43,"stem":44,"number":45,"year":30,"session":12},"fire-107-1-water-chemical-031","惰性氣體滅火設備進行性能檢查時，對於滅火藥劑量判定方法，藥劑量測定結果與重量表、圖面明細表或原廠技術手冊規範等資料核對，其差值應在充填值多少以下？",31,{"webId":47,"stem":48,"number":49,"year":30,"session":12},"fire-107-1-water-chemical-037","有關撒水頭設置之敘述，下列何者正確？",37,[51,55,59,63,67],{"webId":52,"year":53,"stem":54,"number":13},"fire-111-1-water-chemical-036",111,"二氧化碳滅火設備，採用低壓式滅火藥劑儲存容器時，壓力在何範圍會發出警報？",{"webId":56,"year":57,"stem":58,"number":13},"fire-110-1-water-chemical-036",110,"依消防安全設備及必要檢修項目檢修基準，自動撒水設備之加壓送水裝置，在減壓措施方面，補助撒水栓放水壓力應在 X kgf\u002Fcm2 以上 Y kgf\u002Fcm2 以下。X、Y 分別為何？",{"webId":60,"year":61,"stem":62,"number":13},"fire-109-1-water-chemical-036",109,"任一消防專用蓄水池至建築物各部分之水平距離不得超過多少公尺？",{"webId":64,"year":65,"stem":66,"number":13},"fire-108-1-water-chemical-036",108,"依各類場所消防安全設備設置標準之規定，高發泡放出口在全區放射防護區域內，樓地板面積每多少平方公尺應至少設置 1 個，且能有效放射至該區域，並附設泡沫放出停止裝置？",{"webId":40,"year":30,"stem":41,"number":13},true,1785123165602]