[{"data":1,"prerenderedAt":70},["ShallowReactive",2],{"q-fire-114-1-alarm-evacuation-004":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":27,"sameNumber":53,"hasEssay":26},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":25,"freq":12,"indexable":26},"fire-114-1-警報與避難系統消防安全設備概要-004","fire-114-1-alarm-evacuation-004",114,1,4,"某電影院放映場所火警自動警報設備所使用之蓄積型偵煙探測器有 10 秒之蓄積時間，其所使用之中繼器有 10 秒之蓄積時間，則其受信總機之蓄積時間，最多可為多少秒？",{"A":16,"B":17,"C":18,"D":19},"60 秒","20 秒","50 秒","40 秒","D",null,[],false,"本題考點：火警自動警報設備採蓄積型偵煙探測器時，探測器、中繼器與受信總機三者蓄積時間的合計上限規定。\n【正解理由】依《各類場所消防安全設備設置標準》關於火警自動警報設備之規定，蓄積型探測器、中繼器與受信總機所設定之蓄積時間，合計不得超過60秒；本題探測器已用10秒、中繼器已用10秒，受信總機可分配的餘額為60秒扣除20秒後之40秒，故選D。\n【演算步驟】\n合計上限：T總 = 60 秒。\n已佔用：探測器 10 秒 + 中繼器 10 秒 = 20 秒。\n受信總機可設定上限：T受 = 60 秒 − 20 秒 = 40 秒。\n【逐項排除】\n(A) 60秒是三者合計的總上限，若受信總機單獨設為60秒，加計探測器與中繼器後合計達80秒，已逾法定上限。\n(B) 20秒僅為探測器與中繼器已佔用的時間，並非受信總機的可用餘額，屬看錯所問對象的誘答。\n(C) 50秒是以60秒僅扣除單一裝置10秒所得，漏算另一個裝置的蓄積時間，合計將達70秒而超限。\n(D) 40秒使三者合計恰為60秒，未逾上限且將蓄積時間用到最大值，符合題目所問「最多可為多少秒」，正確。\n【記憶點】蓄積時間三段相加不得超過60秒，受信總機能拿到的就是60減去前面兩段。","蓄積型探測器的設計目的是抑制非火災報。偵煙探測器對水蒸氣、油煙、粉塵、香菸煙都會有反應，若感測到煙就立刻發報，在廚房附近、吸菸區、放映場所這類環境會產生大量誤報，久而久之現場人員把警報當成噪音，真正火災時反而失去警覺，這是設備可靠度的最大殺手。所謂蓄積，就是探測器偵知煙濃度達到動作值後不立即發信，而是持續一段時間確認煙持續存在才送出火災信號，短暫的水蒸氣或菸霧在確認期間即消散，訊號自然不成立。\n蓄積可以發生在三個位置：探測器本身、中繼器、受信總機。條文對各段與總和都設限，其立法理由是延遲確認雖能減少誤報，但每一秒延遲都直接壓縮避難時間，因此在誤報抑制與早期發現之間必須畫一條界線，60秒即是這條界線。命題方式固定，就是給定其中一或兩段的秒數，要考生換算剩餘可分配值，本題屬最典型的形式。作答時務必看清所問對象是「受信總機最多可設定幾秒」而非「合計幾秒」，選項中通常會同時放進總上限與已佔用值當陷阱。\n設置面上還有幾個相關規定必須一併掌握。使用蓄積型探測器的樓層，其警戒範圍內若同時裝設非蓄積型探測器，動作邏輯的整合須留意；地區音響裝置的鳴動方式在一定規模以上場所採分區鳴動，起火層與其直上層先鳴動，之後再擴及全棟，這與蓄積時間同屬「時間管理」概念，常一起出題。此外，探測器種類的選用邏輯也是常客：偵煙式適用走廊、樓梯、通道與電信機械室等易早期發煙處；定溫式適用廚房、鍋爐房等平時即有煙或高溫之場所，避免誤報；差動式適用一般居室，靠溫升速率動作。放映場所因暗室且有投影燈熱源與人員吸菸的歷史背景，正是蓄積型偵煙探測器的典型適用場合，題幹設定電影院並非隨意。\n把「蓄積上限60秒、三段相加」與「探測器選用場所對照」兩張表背熟，這一節的計算題與判斷題就能一併掌握。",true,[28,32,36,40,44,49],{"webId":29,"stem":30,"number":13,"year":31,"session":12},"fire-112-1-alarm-evacuation-004","依據一一九火災通報裝置檢修基準之性能檢查，下列何者非預備電源檢查方法之項目？",112,{"webId":33,"stem":34,"number":12,"year":35,"session":12},"fire-106-1-alarm-evacuation-001","某一 KTV 視聽歌唱場所設於大樓地下層，依規定樓地板面積如合計超過多少，應設置瓦斯漏氣火警自動警報設備？",106,{"webId":37,"stem":38,"number":12,"year":39,"session":12},"fire-111-1-alarm-evacuation-001","依各類場所消防安全設備設置標準規定，公共危險物品室內儲存場所總樓地板面積在多少平方公尺以上者，應設置火警自動警報設備？",111,{"webId":41,"stem":42,"number":43,"year":35,"session":12},"fire-106-1-alarm-evacuation-002","對於消防安全設備緊急供電系統之配線之規定，下列何者正確？",2,{"webId":45,"stem":46,"number":47,"year":48,"session":12},"fire-110-1-alarm-evacuation-040","避難器具之裝設規定，下列何者正確？",40,110,{"webId":50,"stem":51,"number":52,"year":35,"session":12},"fire-106-1-alarm-evacuation-003","裝設緊急廣播設備之建築物之規定，下列何者錯誤？",3,[54,55,58,62,66],{"webId":29,"year":31,"stem":30,"number":13},{"webId":56,"year":48,"stem":57,"number":13},"fire-110-1-alarm-evacuation-004","有一棟總樓地板面積 4,000 平方公尺的七層辦公建築物，當起火層為地上第二層時，下列有關其火警自動警報設備分區鳴動方式的敘述，何者正確？",{"webId":59,"year":60,"stem":61,"number":13},"fire-109-1-alarm-evacuation-004",109,"某火警受信總機設有 15 回路，進行回路能否同時動作測試時，應不要復舊使任意幾回路進行測試？",{"webId":63,"year":64,"stem":65,"number":13},"fire-108-1-alarm-evacuation-004",108,"某一防火構造建築物，地上 5 層且為無開口樓層，1 至 2 層供辦公室用途使用，3 至 5 層供餐廳用途使用，各樓層樓地板面積皆為 200 平方公尺，依照各類場所消防安全設備設置標準之規定，請問本場所火警自動警報設備之設置情形，下列何者正確？",{"webId":67,"year":68,"stem":69,"number":13},"fire-107-1-alarm-evacuation-004",107,"下列那一種探測器，不可以裝設於室內天花板或屋頂板高度 15 公尺以上未滿 20 公尺之空間？",1785123169115]