[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-114-1-alarm-evacuation-037":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":25,"sameNumber":50,"hasEssay":68},"警報與避難系統消防安全設備概要","alarm-evacuation","警報與避難 · Alarm & Egress","警報與避難系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":24,"freq":12,"indexable":23},"fire-114-1-警報與避難系統消防安全設備概要-037","fire-114-1-alarm-evacuation-037",114,1,37,"兩棟旅館欲以過廊連接，並分別各自檢討消防設備，下列相關規定何者正確？",{"A":16,"B":17,"C":18,"D":19},"應僅供通行或搬運用途使用，若供其他用途使用須為防火構造或不燃材料","為避免延燒，兩棟旅館之間距，1 樓超過 6 公尺，2 樓以上超過 10 公尺，過廊應無通行之障礙，有效寬度應超過 6 公尺以利避難疏散","兩棟旅館之間距若小於設置標準規定，過廊須為開放式或檢討連接建築物之外牆及屋頂與過廊間距 3 公尺以內的部分需防火構造或不燃材料，並檢討開口狀況","兩棟旅館之間距若小於設置標準規定，且過廊設置有遮蔽風雨之頂棚或構造者，需有直接開向室外之開口面積合計在過廊面積的百方之二以上","C",null,[],false,"",[26,31,35,39,43,47],{"webId":27,"stem":28,"number":29,"year":30,"session":12},"fire-109-1-alarm-evacuation-033","有關緊急電源插座外觀檢查之判定方法，下列何者與各類場所消防安全設備檢修及申報作業基準之規定不同？",33,109,{"webId":32,"stem":33,"number":34,"year":30,"session":12},"fire-109-1-alarm-evacuation-035","有關避難器具開口部周圍狀況外觀檢查之判定方法，下列何者與各類場所消防安全設備檢修及申報作業基準之規定不同？",35,{"webId":36,"stem":37,"number":38,"year":30,"session":12},"fire-109-1-alarm-evacuation-032","有關無線電通信輔助設備保護箱標示之外觀檢查的判定方法，下列何者與各類場所消防安全設備檢修及申報作業基準之規定不同？",32,{"webId":40,"stem":41,"number":42,"year":30,"session":12},"fire-109-1-alarm-evacuation-036","有關定溫式感知線型探測器之外觀試驗判定要領，下列何者與消防安全設備測試報告書測試方法及判定要領之規定不同？",36,{"webId":44,"stem":45,"number":46,"year":30,"session":12},"fire-109-1-alarm-evacuation-031","有關緊急照明設備性能檢查之判定方法與注意事項，下列何者與各類場所消防安全設備檢修及申報作業基準之規定不同？",31,{"webId":48,"stem":49,"number":13,"year":30,"session":12},"fire-109-1-alarm-evacuation-037","有關警報系統消防安全設備設置，下列何者與各類場所消防安全設備設置標準之規定不同？",[51,55,56,60,64],{"webId":52,"year":53,"stem":54,"number":13},"fire-110-1-alarm-evacuation-037",110,"下列有關緊急電源插座之設置，何者錯誤？",{"webId":48,"year":30,"stem":49,"number":13},{"webId":57,"year":58,"stem":59,"number":13},"fire-108-1-alarm-evacuation-037",108,"某機場候機室樓地板面積 300 m2，自然排煙設備其窗戶都在天花板或其下方 80 公分範圍內，共有 10 扇窗，採正向由上往外推可達 90°，請問每一扇窗面積多大才合格？",{"webId":61,"year":62,"stem":63,"number":13},"fire-107-1-alarm-evacuation-037",107,"設置避難器具時，標示其設置位置、使用方法並設置指標，下列規定何者錯誤？",{"webId":65,"year":66,"stem":67,"number":13},"fire-106-1-alarm-evacuation-037",106,"為避免探測死角，在安裝光電式分離型探測器時，其受光器及送光器應設在距其背部牆壁多少公分範圍內？",true,1785123169424]