[{"data":1,"prerenderedAt":68},["ShallowReactive",2],{"q-fire-114-1-water-chemical-005":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":25,"sameNumber":50,"hasEssay":67},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":24,"freq":12,"indexable":23},"fire-114-1-水與化學系統消防安全設備概要-005","fire-114-1-water-chemical-005",114,1,5,"惰性氣體及鹵化烴滅火設備之防護區域竣工時，應做防護區域完整性測試，X 分鐘內之氣體洩漏量使滅火藥劑維持在設計濃度 Y %以上者為合格。則 X、Y 各為何？",{"A":16,"B":17,"C":18,"D":19},"X=10、Y=85","X =20、Y =90","X =10、Y=95","X =5、Y =80","A",null,[],false,"",[26,31,35,38,41,46],{"webId":27,"stem":28,"number":29,"year":30,"session":12},"fire-108-1-water-chemical-002","自動撒水設備竣工時，應做加壓試驗。但密閉乾式管系應併行空氣壓試驗，試驗時，應使空氣壓力達到 X MPa 之標準，其壓力持續 Y 小時，漏氣減壓量應在 Z MPa 以下為合格。X、Y、Z 分別為何？",2,108,{"webId":32,"stem":33,"number":34,"year":30,"session":12},"fire-108-1-water-chemical-004","密閉乾式或預動式自動撒水設備，下列設置規定何者正確？",4,{"webId":36,"stem":37,"number":12,"year":30,"session":12},"fire-108-1-water-chemical-001","在應設置室內消防栓設備之場所，但設有室外消防栓設備時，在第一層水平距離 X 公尺以下、第二層步行距離 Y 公尺以下有效滅火範圍內，室內消防栓設備限於第一層、第二層免設。X、Y 分別為何？",{"webId":39,"stem":40,"number":13,"year":30,"session":12},"fire-108-1-water-chemical-005","開放式自動撒水設備之自動及手動啟動裝置，下列設置規定何者正確？",{"webId":42,"stem":43,"number":44,"year":45,"session":12},"fire-107-1-water-chemical-040","進行幫浦性能試驗時，幫浦之出水量在額定出水量之 1.5 倍時，其全揚程應為額定出水量在性能曲線上全揚程百分之多少以上？",40,107,{"webId":47,"stem":48,"number":49,"year":30,"session":12},"fire-108-1-water-chemical-006","使用密閉式撒水頭之自動撒水設備末端之查驗閥，下列設置規定何者正確？",6,[51,55,59,63,64],{"webId":52,"year":53,"stem":54,"number":13},"fire-111-1-water-chemical-005",111,"有關移動式泡沫滅火設備，依各類場所消防安全設備設置標準之規定，下列敘述何者正確？",{"webId":56,"year":57,"stem":58,"number":13},"fire-110-1-water-chemical-005",110,"消防幫浦加壓送水裝置之啟動用水壓開關裝置，下列規定何者正確？",{"webId":60,"year":61,"stem":62,"number":13},"fire-109-1-water-chemical-005",109,"某電信機械室設置二氧化碳全區放射滅火設備，其核算之滅火藥劑量應於多少時間內全部放射完畢？",{"webId":39,"year":30,"stem":40,"number":13},{"webId":65,"year":45,"stem":66,"number":13},"fire-107-1-water-chemical-005","泡沫滅火設備使用泡沫噴頭時，每一放射區域之樓地板面積規定應為何？",true,1785123164868]