[{"data":1,"prerenderedAt":68},["ShallowReactive",2],{"q-fire-115-1-water-chemical-001":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":24,"sameNumber":50,"hasEssay":67},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":12,"stem":13,"options":14,"answer":19,"answerNote":20,"images":21,"imagesPending":22,"lawTimestamp":11,"explanation":23,"explanationDeep":23,"freq":12,"indexable":22},"fire-115-1-水與化學系統消防安全設備概要-001","fire-115-1-water-chemical-001",115,1,"有關消防幫浦性能試驗，下列敘述何者錯誤？",{"A":15,"B":16,"C":17,"D":18},"消防幫浦出水量在額定出水量時，其性能曲線上之全揚程必須達額定揚程之 100%至 110%之間","消防幫浦出水量在額定出水量之 150%時，其性能曲線上之全揚程必須達額定揚程之 65%以上","全閉揚程應為額定出水量在性能曲線上全揚程之 140%以上","消防幫浦二次測壓力錶所顯示壓力值 1 kg\u002Fcm2 約等於 10 公尺揚程","C",null,[],false,"",[25,30,34,38,42,46],{"webId":26,"stem":27,"number":28,"year":29,"session":12},"fire-108-1-water-chemical-038","依各類場所消防安全設備檢修及申報作業基準，有關乾粉滅火藥劑判定方法，乾粉藥劑不得有雜質、變質、固化等情形，且以手輕握搓揉，並自地面上高度多少公分處使其落下，應呈粉狀？",38,108,{"webId":31,"stem":32,"number":33,"year":29,"session":12},"fire-108-1-water-chemical-040","電動機之使用應符合之相關規定，下列何者錯誤？",40,{"webId":35,"stem":36,"number":37,"year":29,"session":12},"fire-108-1-water-chemical-037","進行滅火器之檢查時，有關一般注意事項，下列何者錯誤？",37,{"webId":39,"stem":40,"number":12,"year":41,"session":12},"fire-109-1-water-chemical-001","下列場所何者未達依法應設置滅火器之條件？",109,{"webId":43,"stem":44,"number":45,"year":29,"session":12},"fire-108-1-water-chemical-036","依各類場所消防安全設備設置標準之規定，高發泡放出口在全區放射防護區域內，樓地板面積每多少平方公尺應至少設置 1 個，且能有效放射至該區域，並附設泡沫放出停止裝置？",36,{"webId":47,"stem":48,"number":49,"year":41,"session":12},"fire-109-1-water-chemical-002","某地下一層、地上七層建築物，地下層為室內停車空間，面積 200 平方公尺，一至七層為集合住宅，各層面積 100 平方公尺，有室內安全梯直通地下層，本案是否需設置室內消防栓設備？",2,[51,55,59,60,63],{"webId":52,"year":53,"stem":54,"number":12},"fire-111-1-water-chemical-001",111,"依各類場所消防安全設備設置標準規定，下列何種場所不需設置室外消防栓設備？",{"webId":56,"year":57,"stem":58,"number":12},"fire-110-1-water-chemical-001",110,"公共危險物品等場所消防設計及消防安全設備，電氣設備使用之處所，每多少平方公尺（含未滿）應設置第五種滅火設備一具以上？",{"webId":39,"year":41,"stem":40,"number":12},{"webId":61,"year":29,"stem":62,"number":12},"fire-108-1-water-chemical-001","在應設置室內消防栓設備之場所，但設有室外消防栓設備時，在第一層水平距離 X 公尺以下、第二層步行距離 Y 公尺以下有效滅火範圍內，室內消防栓設備限於第一層、第二層免設。X、Y 分別為何？",{"webId":64,"year":65,"stem":66,"number":12},"fire-107-1-water-chemical-001",107,"撒水頭之設置位置規定中，撒水頭迴水板下方 A 公分內及水平方向 B 公分內，應保持淨空間，不得有障礙物，其中 A、B 分別為下列何者？",true,1785123164442]