[{"data":1,"prerenderedAt":69},["ShallowReactive",2],{"q-fire-115-1-water-chemical-039":3},{"subject":4,"subjectSlug":5,"subjectKicker":6,"subjectShort":7,"question":8,"related":25,"sameNumber":50,"hasEssay":68},"水與化學系統消防安全設備概要","water-chemical","水與化學系統 · Water & Chemical","水與化學系統",{"id":9,"webId":10,"year":11,"session":12,"subject":4,"number":13,"stem":14,"options":15,"answer":20,"answerNote":21,"images":22,"imagesPending":23,"lawTimestamp":11,"explanation":24,"explanationDeep":24,"freq":12,"indexable":23},"fire-115-1-水與化學系統消防安全設備概要-039","fire-115-1-water-chemical-039",115,1,39,"關於乾粉滅火設備加、蓄壓用氣體量，下列敘述何者正確？",{"A":16,"B":17,"C":18,"D":19},"加壓用氣體使用氮氣時，在溫度攝氏三十五度，大氣壓力（表壓力）每平方公分零公斤狀態下，每一公斤乾粉藥劑需氮氣二十公升以上","加壓用氣體使用二氧化碳時，每一公斤乾粉藥劑需二氧化碳二十公克","蓄壓用氣體使用氮氣時，在溫度攝氏三十五度，大氣壓力（表壓力）每平方公分零公斤狀態下，每一公斤乾粉藥劑需氮氣二十公升以上，並加算清洗配管所需要量以上","蓄壓用氣體使用二氧化碳時，每一公斤乾粉藥劑需二氧化碳二十公克並加算清洗配管所需要量以上","D",null,[],false,"",[26,31,35,39,43,47],{"webId":27,"stem":28,"number":29,"year":30,"session":12},"fire-109-1-water-chemical-035","廚房等大量使用火源之處所，多少樓地板面積需有一滅火效能值？",35,109,{"webId":32,"stem":33,"number":34,"year":30,"session":12},"fire-109-1-water-chemical-037","連結送水管之配管設置規定，應能承受送水設計壓力 1.5 倍以上之水壓，且能持續多少時間才合格？",37,{"webId":36,"stem":37,"number":38,"year":30,"session":12},"fire-109-1-water-chemical-034","乾粉滅火設備使用加壓或蓄壓用氣體容器，其所使用之氣體為下列何者？",34,{"webId":40,"stem":41,"number":42,"year":30,"session":12},"fire-109-1-water-chemical-038","消防專用蓄水池之設置規定，下列何者正確？",38,{"webId":44,"stem":45,"number":46,"year":30,"session":12},"fire-109-1-water-chemical-033","加壓式乾粉滅火設備應設壓力調整裝置，其可調整壓力至每平方公分多少公斤以下？",33,{"webId":48,"stem":49,"number":13,"year":30,"session":12},"fire-109-1-water-chemical-039","公共危險品等場所中，所設置之室外消防栓設備，其緊急電源之供電容量應供其有效動作多久以上？",[51,55,59,60,64],{"webId":52,"year":53,"stem":54,"number":13},"fire-111-1-water-chemical-039",111,"可燃性高壓氣體儲存場所任一點至滅火器之步行距離在 X 公尺以下，並不得妨礙出入作業；每具滅火器對普通火災具有 Y 個以上之滅火效能值，請問前述 X、Y 為何？",{"webId":56,"year":57,"stem":58,"number":13},"fire-110-1-water-chemical-039",110,"依消防安全設備及必要檢修項目檢修基準，冷卻撒水設備之遠隔啟動裝置，限用於儲存閃火點多少℃以下公共危險物品之室外儲槽？",{"webId":48,"year":30,"stem":49,"number":13},{"webId":61,"year":62,"stem":63,"number":13},"fire-108-1-water-chemical-039",108,"依各類場所消防安全設備設置標準之規定，公共危險物品室外儲槽場所之冷卻撒水設備如以幫浦方式進行加壓時，實際測得之放射量除以該冷卻撒水噴頭（噴孔）所防護儲槽側壁面積應在多少以上？",{"webId":65,"year":66,"stem":67,"number":13},"fire-107-1-water-chemical-039",107,"為執行檢修申報，針對水霧滅火系統綜合檢查，對於判定方法之敘述，下列何者正確？",true,1785123164812]